Liquid-to-Liquid Plate Heat Exchanger for CDU Systems | CST

Views: 0     Author: Site Editor     Publish Time: 2026-11-25      Origin: Site

A liquid-to-liquid plate heat exchanger for a Coolant Distribution Unit (CDU) transfers heat between a facility-water circuit and a clean secondary technology-cooling circuit without allowing the two fluids to mix. In a GPU or HPC data center, the secondary circuit can circulate coolant to direct-to-chip cold plates, rack manifolds, rear-door heat exchangers or other liquid-cooled IT equipment, while the facility side rejects the collected heat through the central cooling plant.

At CSTHEATEXCHANGER, we develop liquid-to-liquid plate heat exchangers for CDU packages used in hyperscale data centers, AI computing clusters, high-performance computing rooms, liquid-cooled server halls and modular edge facilities. We select the plate pattern, connection layout, gasket or welded construction, wetted materials and frame arrangement from the real heat load, coolant chemistry, flow rate, temperature program, allowable pressure drop and maintenance requirements.

The numerical values in this article are typical engineering references or illustrative examples, not confirmed CST product ratings. Final capacity, approach temperature, flow, pressure drop, plate material, gasket material, design pressure, inspection plan and acceptance criteria require project-specific calculation and approval.

Liquid-to-Liquid Plate Heat Exchangers for CDU Data Center Cooling Systems.jpg

1. Why the Plate Heat Exchanger Is the Thermal Core of a CDU

A CDU is more than a pump skid. It is the controlled interface between the data center facility loop and the technology loop serving liquid-cooled IT equipment. Within that interface, the liquid-to-liquid plate heat exchanger performs four important functions:

  • Transfers heat from the secondary coolant to facility water.

  • Keeps the facility-water chemistry separate from the server-side coolant.

  • Provides a compact heat-transfer surface for a high-density CDU package.

  • Establishes the thermal approach and pressure-drop conditions that influence the complete cooling loop.

For direct-to-chip cooling, the heat exchanger must be selected together with the GPU cold plates, rack manifolds, hoses, quick disconnects, pumps and facility-water system. A plate heat exchanger that appears suitable by nominal kilowatt capacity may be unsuitable if its pressure drop, fouling allowance, material compatibility or control range does not match the rest of the system.

Basic CDU Heat-Transfer Path

Facility-water circuit                         Secondary technology circuit

Facility-water inlet                           Warm coolant return from GPU racks
          │                                                │
          ▼                                                ▼
   ┌─────────────────────────────────────────────────────────────┐
   │        Liquid-to-liquid plate heat exchanger               │
   │                                                             │
   │  Facility channel      Plate pack       Secondary channel   │
   │  removes heat  ─────►  transfers  ◄────  returns cooler     │
   │                                                             │
   └─────────────────────────────────────────────────────────────┘
          │                                                │
          ▼                                                ▼
Facility-water return                           Coolant supply to cold plates

The two circuits exchange heat through the plate pack. They remain physically separated unless a plate, gasket, weld or connection failure occurs. The final CDU should therefore include an appropriate leak-detection and alarm strategy for the project risk profile.

2. Plate Heat Exchanger Construction for CDU Applications

2.1 Gasketed Plate Heat Exchanger

A gasketed plate heat exchanger uses removable plates sealed by elastomeric gaskets and compressed in a frame. This construction can be suitable when the project prioritizes service access, plate inspection, capacity adjustment or replaceable gaskets.

Potential advantages include:

  • Serviceable plate pack.

  • Possibility of adding or removing plates after a design review.

  • Separate primary and secondary flow passages.

  • Flexible port and frame arrangements.

  • Straightforward cleaning access when the installation provides enough clearance.

The gasket material must be compatible with the coolant, temperature, pressure, cleaning procedure and expected operating cycle. A gasket selection should not be based on water service alone when glycol, additives or special coolants are present.

2.2 Brazed Plate Heat Exchanger

A brazed plate heat exchanger uses a permanently joined plate pack. It is often considered for compact CDU assemblies where a small footprint and low external leakage risk are important.

Potential advantages include:

  • Compact construction.

  • Low mass compared with a large framed unit.

  • Few external sealing components.

  • Suitability for modular rack-side or in-row CDU packages.

Because the plate pack is not normally opened for routine inspection, fluid cleanliness, filtration, start-up flushing and chemistry control are especially important. The final construction must also be checked against project requirements for pressure containment, serviceability and repair strategy.

2.3 Welded or Semi-Welded Plate Construction

Welded or semi-welded plate heat exchangers may be considered where the coolant, temperature, pressure or contamination risk makes a fully gasketed arrangement less suitable. They can also be used where the customer requires a particular material or leak-resistance approach.

The welding process, non-destructive inspection, pressure test and repair method must be included in the manufacturing and acceptance plan. No welding standard or certification should be assumed unless it is stated in the approved project documentation.

3. Counter-Flow Arrangement and Thermal Approach

A counter-flow plate heat exchanger generally places the warm secondary return against the cooler facility-water stream along the heat-transfer path. This arrangement can support a small temperature approach when the flow rates, plate pattern, surface area and fluid properties are suitable.

However, a small approach temperature is not automatically better. It may require:

  • More heat-transfer area.

  • More plates or a larger frame.

  • Higher flow rates.

  • Greater pressure drop.

  • More demanding control at low load.

  • Increased sensitivity to fouling or flow imbalance.

For a CDU, the correct objective is not simply the smallest possible approach. It is a balanced selection that meets the IT coolant temperature target while keeping pump energy, equipment size, pressure drop and service requirements within the project limits.

Thermal Balance

A simplified heat balance can be expressed as:

Heat transferred ≈ mass flow × specific heat × temperature change

The design calculation should use the real coolant properties at the operating temperature. Glycol concentration, viscosity and specific heat can materially change the required flow and pressure drop compared with treated water.

4. Design Inputs Required Before Selecting a CDU Plate Heat Exchanger

We recommend collecting the following inputs before choosing a plate pattern or frame size.

Secondary Technology Loop

  • Total and per-rack heat load.

  • Current load, peak design load and future expansion load.

  • Supply and return coolant temperatures.

  • Minimum, normal and maximum flow.

  • Coolant type and concentration.

  • Conductivity, pH, inhibitor package and contamination limits.

  • Maximum allowable pressure drop.

  • Cold-plate and rack-manifold pressure limits.

  • Required filtration and particle-control level.

Facility-Water Loop

  • Facility-water inlet and return temperatures.

  • Available flow at the CDU connection.

  • Minimum and maximum operating pressure.

  • Water-treatment method and chemistry.

  • Suspended solids and fouling risk.

  • Seasonal operating conditions.

  • Facility-side pressure-drop allowance.

  • Isolation, bypass and maintenance requirements.

Mechanical and Controls Interface

  • Installation location: rack-side, in-row, technical room or skid.

  • Connection size, orientation and flange standard.

  • Available footprint, height, weight and service clearance.

  • Pump arrangement and control range.

  • BMS or DCIM communication protocol.

  • Leak-detection method.

  • Alarm priority and shutdown sequence.

  • Factory acceptance test and site commissioning requirements.

Without these inputs, a capacity-only selection can create a mismatch between the plate heat exchanger and the rest of the CDU system.

5. Material Selection and Coolant Compatibility

The plate heat exchanger is exposed to two fluids, not one. Both channels must be reviewed independently and together.

Stainless Steel Plate Materials

Stainless steel plates may be considered for many treated-water and glycol-water loops. The final grade depends on chloride concentration, temperature, cleaning chemicals, water-treatment program and customer material requirements.

Titanium Plate Materials

Titanium may be considered when the fluid chemistry or corrosion risk requires a higher level of resistance than the selected stainless steel construction can provide. It should be selected from the actual water analysis and project duty, not merely because the application is a data center.

Copper-Brazed Construction

A brazed plate heat exchanger may use a copper or another project-approved brazing material. The brazing material must be reviewed against coolant chemistry, conductivity, corrosion risk and any restrictions on metal ions in the secondary loop.

Gaskets and Seals

Gaskets, O-rings, pump seals and valve seats must be compatible with:

  • Water or glycol concentration.

  • Additives and corrosion inhibitors.

  • Operating and cleaning temperatures.

  • Pressure cycling.

  • Any customer-specified dielectric or engineered coolant.

CSTHEATEXCHANGER can develop the plate heat exchanger around customer-approved materials. Material and corrosion claims remain subject to coolant analysis, engineering review and the approved bill of materials.

6. Pressure Drop: The CDU Selection Constraint Often Missed

A plate heat exchanger with more plates does not automatically produce the best CDU. The designer must balance heat-transfer area against pressure drop on both circuits.

Pressure loss may be affected by:

  • Plate corrugation pattern.

  • Number of plates.

  • Channel gap.

  • Flow distribution.

  • Port diameter.

  • Fluid viscosity.

  • Glycol concentration.

  • Fouling allowance.

  • Partial-load operation.

A high pressure drop increases pump power and may reduce the flow available to distant racks. A very low pressure drop design may require a larger heat exchanger or may not provide sufficient turbulence for the required heat transfer.

The selection should provide pressure-drop results for at least the minimum, normal and maximum flow conditions. Where the CDU serves several racks, the plate heat exchanger calculation should be checked against the complete branch-network model.

7. Filtration, Flushing and Water Quality

Plate heat exchangers perform best when the fluid entering the channels is clean and controlled. Small particles can obstruct narrow channels, damage valves or reduce flow through cold plates.

A CDU design should define:

  1. Start-up flushing procedure.

  2. Temporary construction-strainer arrangement.

  3. Permanent filter or strainer location.

  4. Filter differential-pressure alarm.

  5. Water-treatment and sampling schedule.

  6. Filling and air-removal method.

  7. Drain and isolation points.

  8. Cleaning or replacement procedure.

  9. Acceptable conductivity, pH and inhibitor limits.

  10. Response to contamination or cross-fluid leakage.

The filter grade must be coordinated with the cold-plate supplier. A filter that is too coarse may not protect the cold plates; a filter that is too fine may create unnecessary pressure loss and maintenance burden.

8. Plate Heat Exchanger Integration Inside a CDU

The plate heat exchanger is one component of a larger package. Its connections and control behavior must match the other CDU components.

Secondary Pump Arrangement

The pump should be selected from the calculated secondary-loop system curve. A duty/standby arrangement may be considered for critical clusters, but the redundancy boundary must be clear. If the plate heat exchanger, electrical supply or facility-water branch is common, a standby pump alone does not create complete cooling-path redundancy.

Bypass and Minimum Flow

A bypass may be used to maintain minimum flow, support commissioning or stabilize control during low-load operation. The bypass position and control sequence must not allow the secondary loop to lose the flow required by the connected cold plates.

Expansion and Air Removal

The CDU may include an expansion vessel, air separator, automatic vent, drain and fill connections. The size and location depend on loop volume, operating temperature, fluid expansion and installation height.

Leak Detection

Leak detection can be installed around the plate heat exchanger, pump assembly, valve group or drip tray. The alarm sequence should define whether the CDU reduces flow, isolates a circuit, stops the pump or sends a warning to the BMS/DCIM system.

Sensors and Control Points

Typical measurement points include:

  • Facility-water inlet temperature.

  • Facility-water outlet temperature.

  • Secondary coolant supply temperature.

  • Secondary coolant return temperature.

  • Secondary flow rate.

  • Secondary differential pressure.

  • Filter differential pressure.

  • Pump status and speed.

  • Leak status.

  • Expansion-vessel or tank level, where applicable.

The exact point list should be approved before panel fabrication and software commissioning.

9. Indicative Engineering Reference Table

The following values are early-stage reference ranges only. They must not be used as an approved CST datasheet or procurement specification.

Item

Typical or illustrative reference

Project approval required

CDU heat-transfer duty

Approximately 50 kW to 1,500 kW per module; multiple modules may be used for larger clusters

IT load, diversity and expansion calculation

Plate construction

Gasketed, brazed, welded or semi-welded

Service, coolant and pressure requirements

Secondary flow

Approximately 5 to 300 m³/h for selected module ranges

Coolant properties and heat balance

Secondary temperature program

Project-defined; often a moderate-temperature liquid-cooling loop

Cold-plate and server limits

Facility-water temperature program

Project-defined by the central plant

Chiller, dry cooler or cooling-tower conditions

Design pressure

Common project ranges may fall within approximately 6 to 16 bar

Piping class and component ratings

Allowable pressure drop

Customer-defined for each circuit

Pump curve and rack hydraulic model

Wetted material

Stainless steel, titanium or other approved materials

Water analysis and compatibility review

Connection layout

Top, side, bottom or custom orientation

CDU frame and site-piping drawings

Control interface

Modbus, BACnet, dry contacts or customer protocol

BMS/DCIM point list

Testing

Pressure, leak, control and performance tests as specified

FAT protocol and acceptance criteria

These figures describe a possible design envelope, not a guaranteed performance level.

10. Quality and Factory Testing Plan

A project-specific CDU plate heat exchanger can be tested according to the agreed inspection and acceptance plan. Possible checks include:

Dimensional and Visual Inspection

  • Plate pack or shell dimensions.

  • Connection orientation.

  • Frame and support condition.

  • Gasket seating or brazed construction.

  • Nameplate and flow-direction marking.

  • Drain, vent and sensor-port locations.

Pressure and Leak Testing

Pressure and leak tests should be conducted using the project-approved method and limits. The test pressure must be compatible with the design pressure, construction type and applicable customer specification.

Performance Verification

Where required, the factory test may verify flow, temperature, heat-transfer duty and pressure drop at defined test points. The test fluid, instrumentation accuracy, stabilization time and acceptance tolerances should be agreed before testing.

Controls and Alarm Testing

The test plan may include:

  • Pump start and stop.

  • Speed modulation.

  • High-temperature alarm.

  • Low-flow alarm.

  • High filter differential pressure.

  • Sensor failure.

  • Leak detection.

  • Communication loss.

  • Automatic changeover for standby pumps.

  • Manual override and safe shutdown.

CSTHEATEXCHANGER can prepare a test plan around the customer’s FAT requirements. The final test scope must be stated in the purchase and technical documents.

11. Applications for CDU Plate Heat Exchangers

Direct-to-Chip GPU Clusters

The CDU serves cold plates installed on GPUs, CPUs or other high-power components. The primary design concerns are coolant cleanliness, connector pressure drop, minimum flow, supply-temperature stability and rack-level flow balancing.

HPC and Scientific Computing

HPC systems may combine CPU cooling, GPU cooling, memory cooling and high-flow rack manifolds. The plate heat exchanger should be selected from the combined load and pressure-drop model rather than a single-server value.

Rear-Door Heat Exchangers

A secondary coolant loop can feed rear-door heat exchangers. The temperature program, flow distribution and control response may differ from a direct-to-chip system.

Mixed Cooling Halls

A data hall may contain air-cooled, rear-door-cooled and direct-to-chip racks at the same time. Separate CDU branches or independent temperature zones may be required to avoid forcing one operating condition onto incompatible equipment.

Modular AI Data Centers

For modular data centers, compact brazed or packaged plate heat exchangers can support phased deployment. The design should reserve space and connection capacity for later modules without compromising the initial commissioning process.

12. Frequently Asked Questions

What does a plate heat exchanger do inside a CDU?

It transfers heat from the secondary coolant serving liquid-cooled IT equipment to the facility-water circuit while keeping the two fluids physically separated. Its thermal area, pressure drop and materials strongly influence the CDU’s performance.

Is a brazed plate heat exchanger always the best option for a GPU CDU?

No. A brazed unit may be attractive for compact modular systems, while a gasketed, welded or semi-welded construction may be more appropriate for service access, special coolant chemistry, pressure requirements or customer maintenance policy.

Why is coolant chemistry important?

Coolant chemistry affects corrosion, gasket life, brazing-material compatibility, plate fouling and cold-plate cleanliness. Water, glycol mixtures and engineered coolants can require different materials and treatment limits.

Can one plate heat exchanger support several GPU racks?

Yes, if the heat-transfer capacity, flow range, pressure drop, manifold design and control strategy are sized for the complete connected system. Present load, future load and rack diversity should be included in the calculation.

What causes a CDU plate heat exchanger to foul?

Possible causes include construction debris, inadequate flushing, suspended particles, unsuitable water treatment, corrosion products, biological contamination or incompatible coolant additives. Filtration and a documented commissioning procedure reduce these risks.

Does a small approach temperature always improve the CDU?

Not necessarily. A smaller approach can require more heat-transfer area, higher flow, more pump power and tighter control. The best design balances temperature target, pressure drop, footprint, energy consumption and service requirements.

Can CSTHEATEXCHANGER customize the plate heat exchanger for a CDU project?

Yes. We can develop the heat exchanger construction, plate or tube material, connection arrangement, frame, pump interface, sensors and testing plan around the approved project conditions. Final performance is subject to engineering calculation, drawing review, material confirmation and acceptance testing.

13. Customer Data Required for a Project-Specific Selection

Please confirm the following information before requesting a final selection:

1. Application:
   Direct-to-chip GPU cooling, HPC, rear-door heat exchanger, mixed hall or modular data center

2. Heat load:
   Total current load, peak load, future load, per-rack load and diversity factor

3. Secondary coolant:
   Fluid type, glycol concentration or proprietary coolant, pH, conductivity and inhibitor package

4. Secondary temperatures:
   Supply temperature, return temperature, allowable fluctuation and transient requirements

5. Secondary flow:
   Minimum, normal and maximum flow; allowable pressure drop at the CDU boundary

6. Facility-water side:
   Inlet and return temperatures, available flow, pressure range and water chemistry

7. Heat exchanger construction:
   Gasketed, brazed, welded or semi-welded preference; approved plate and gasket materials

8. Mechanical interfaces:
   Connection size, flange standard, orientation, footprint, height, weight and service clearance

9. Pump and redundancy:
   Pump quantity, duty/standby requirement, variable-speed range and failure response

10. Filtration and water quality:
    Filter grade, differential-pressure alarm, flushing method and sampling requirements

11. Controls:
    Local HMI, Modbus RTU/TCP, BACnet, dry contacts, DCIM point list and alarm priorities

12. Testing and documentation:
    FAT, pressure test, leak test, performance test, material documents and commissioning requirements

Source Custom Liquid-to-Liquid Plate Heat Exchangers from CSTHEATEXCHANGER

At CSTHEATEXCHANGER, we develop liquid-to-liquid plate heat exchangers for CDU packages serving high-density GPU and HPC facilities. Our engineering scope can include:

  • Plate, brazed, welded or semi-welded heat-exchanger concepts.

  • Stainless steel, titanium or other project-approved wetted materials.

  • Custom port sizes, connection directions and frame arrangements.

  • CDU pump and filtration interfaces.

  • Temperature, flow, pressure and leak-monitoring points.

  • BMS/DCIM communication and alarm mapping.

  • Factory testing based on the approved technical specification.

  • Selection support for rack-level, row-level and modular CDU architectures.

Send us your GPU cluster heat load, secondary coolant information, facility-water conditions, temperature targets, allowable pressure drops and mechanical interface drawings. We will review the thermal and hydraulic boundaries before preparing a project-specific liquid-to-liquid plate heat exchanger proposal.