A liquid-to-liquid Coolant Distribution Unit (CDU) separates a data center facility-water loop from a clean secondary technology-cooling loop through a dedicated liquid-to-liquid heat exchanger. The CDU circulates treated coolant to direct-to-chip cold plates, rear-door heat exchangers, rack manifolds or other liquid-cooled IT equipment, while controlling flow, differential pressure, supply temperature, filtration, expansion and alarm signals.
At CSTHEATEXCHANGER, we develop custom liquid-to-liquid CDU assemblies for hyperscale GPU data centers, AI training clusters, high-performance computing rooms, edge computing halls and high-density liquid-cooled server deployments. The system architecture, pump arrangement, heat exchanger plate material, control logic, filtration level and connection design are selected from the actual rack heat load, coolant chemistry, redundancy philosophy, facility-water conditions and project interface requirements.
The figures in this article are typical engineering reference ranges or illustrative examples only. They are not confirmed CST product ratings. Final capacity, temperatures, flow rates, pressure drop, materials, control functions, certifications and enclosure details must be established through project calculations, customer specifications, drawings and selection approval.
Modern GPU clusters create a concentrated and continuously changing thermal load. Compared with conventional air-cooled servers, direct-to-chip liquid cooling transfers a larger share of processor heat into a coolant loop close to the heat source.
A liquid-to-liquid CDU is the interface between that technology loop and the data center facility loop. It can provide:
Hydraulic separation between the facility-water side and the IT-equipment side.
A controlled secondary coolant environment for GPU cold plates and rack manifolds.
Pumped circulation matched to rack-level flow demand.
Temperature and differential-pressure control at the CDU boundary.
Filtration and air-management provisions for the secondary loop.
Leak detection, high-temperature alarms and pump-failure protection.
A scalable path from a single liquid-cooled rack to a larger cluster or row.
The CDU does not replace the complete data center cooling plant. It is a thermal and hydraulic distribution subsystem that must be selected together with the facility-water system, heat rejection equipment, rack manifolds, server cold plates and control network.
FACILITY WATER LOOP SECONDARY TECHNOLOGY LOOP
Cooling plant / chiller GPU cold plates
│ Rack manifolds
│ Rear-door heat exchangers
▼ ▲
┌──────────────────┐ ┌────────────────────────┴───────────────┐
│ Facility-side │ │ Secondary-side pump and control loop │
│ isolation valves │ │ Clean coolant, filtration, expansion │
└────────┬─────────┘ └────────────────────────┬───────────────┘
│ │
▼ │
┌──────────────────────────────────────────────────────────────┐
│ CST Liquid-to-Liquid CDU │
│ │
│ Facility-water inlet │
│ │ │
│ ▼ │
│ ┌───────────────┐ Secondary coolant outlet │
│ │ Plate or │───────────────────────────────────────────┘
│ │ shell-and-tube│
│ │ heat exchanger│◄──────────────── Secondary coolant return
│ └───────────────┘
│ ▲
│ │
│ Facility-water return
│
│ Sensors · Pump package · Filter · Expansion vessel
│ Control panel · Leak detection · BMS communication
└──────────────────────────────────────────────────────────────┘ The two fluid circuits remain separated by the heat exchanger. The exact degree of separation, allowable cross-contamination risk, and leakage-detection approach depend on the project’s fluid chemistry and reliability requirements.
A CDU normally combines heat transfer, fluid circulation, measurement and control in one engineered package.
The primary facility-water circuit removes heat from the secondary technology loop. Depending on the design duty and fluid conditions, the heat exchanger may use:
Brazed or gasketed plate heat exchanger construction.
Welded plate or semi-welded plate construction for selected applications.
Shell-and-tube construction where fluid compatibility, serviceability or pressure requirements favor a tubular design.
Stainless steel, titanium or other project-approved wetted materials.
The heat exchanger must be selected using the actual fluid properties rather than capacity alone. Important inputs include inlet and outlet temperatures, mass flow, specific heat, viscosity, glycol concentration, fouling tendency, allowable pressure drop and required approach temperature.
The secondary pump provides the circulation required by the connected racks and cold plates. A CDU may use one pump, duty/standby pumps, parallel variable-speed pumps or a modular pump arrangement. The appropriate configuration depends on:
Number of connected racks.
Required flow range and control range.
Redundancy target.
Available electrical supply.
Maintenance strategy.
Pressure drop across cold plates, manifolds, hoses and quick disconnects.
Pump selection should be based on the complete system curve. A pump that is oversized for the rack loop can create unnecessary power consumption, noise and control instability; an undersized pump may fail to maintain the required flow at peak load.
The CDU controller can modulate pump speed, control valves or a bypass circuit to maintain a project-defined secondary supply temperature or differential pressure. Common measurements include:
Facility-water inlet and outlet temperature.
Secondary coolant supply and return temperature.
Secondary-loop pressure.
Differential pressure across the CDU or rack branch.
Flow rate.
Filter differential pressure.
Tank level or expansion-vessel pressure, where applicable.
Leak detection and drip-tray status.
Setpoints should be established by the server, cold-plate, rack-manifold and facility-cooling suppliers together. The CDU should not be assigned a universal temperature or pressure target without a system-level review.
A hyperscale project may use a CDU at several different levels:
A row-level CDU serves a defined group of liquid-cooled racks. It can simplify hydraulic zoning and reduce branch-piping length. The package may include a larger heat exchanger, multiple pumps, a larger expansion arrangement and a control cabinet with network communication.
A rack-level CDU is installed close to one rack or a small rack group. It can provide localized control and easier modular deployment, but the project must consider service access, floor loading, acoustic performance, electrical distribution and the number of independent packages.
An in-row CDU is positioned with the rack line and may be integrated into an enclosure or adjacent cabinet. It is suitable when the data hall layout favors short secondary piping runs and modular capacity additions.
A centralized module can distribute coolant to multiple rack branches through a secondary manifold system. This architecture can reduce the number of local pumps, but it requires careful hydraulic balancing, branch isolation and control coordination.
The best architecture depends on rack density, cluster topology, expansion strategy, maintenance access, facility-water routing and the desired failure-domain boundaries.
The following components are commonly considered during CDU development. Their inclusion and final specification are project-dependent.
The liquid-to-liquid heat exchanger is the primary thermal barrier and heat-transfer component. Plate heat exchangers are often selected for compactness and high heat-transfer density. Shell-and-tube units may be selected where serviceability, pressure containment or fluid compatibility is more important than compact footprint.
Variable-speed pumps can adjust coolant flow to changing rack demand. Duty/standby or parallel-pump arrangements may be considered for critical applications, subject to the project’s redundancy and maintenance requirements.
A secondary-loop filter or strainer helps protect cold plates, control valves, quick disconnects and narrow passages from particles. The filter mesh or cartridge rating must be coordinated with the cold-plate manufacturer. Excessively fine filtration can increase pressure drop and maintenance frequency.
A closed secondary loop may require an expansion vessel, air separator, automatic vent, drain connection or filling assembly. The exact arrangement depends on loop volume, operating temperature, fluid expansion and installation height.
Isolation valves, check valves, balancing valves, pressure-relief devices and bypass valves may be included to support commissioning and service. Valve materials and sealing materials must be compatible with the selected coolant.
Leak detection may be based on a drip tray, moisture sensor, cable sensor, pressure-decay logic or a combination of methods. The alarm response should be coordinated with pump shutdown, valve isolation, facility monitoring and operator procedures.
A CDU control panel may support local display, hardwired alarms, dry contacts, Modbus RTU, Modbus TCP, BACnet or another customer-specified interface. The protocol and point list should be confirmed before manufacturing.
Coolant chemistry is one of the most important inputs in a liquid-to-liquid CDU project. The heat exchanger and piping materials should not be selected only by temperature or pressure.
Depending on the project, the secondary circuit may use:
Treated water.
Water and inhibited ethylene glycol.
Water and inhibited propylene glycol.
A customer-specified dielectric or engineered coolant.
The fluid concentration, inhibitor package, conductivity, pH, dissolved oxygen, chloride content and contamination limits should be documented. Final recommendations must be confirmed against the equipment and coolant supplier requirements.
Possible wetted materials include stainless steel, copper alloys, titanium, aluminum and selected polymer components. Material compatibility must account for galvanic couples, chloride exposure, glycol chemistry, operating temperature, cleaning agents and long-term water treatment.
CSTHEATEXCHANGER can develop the heat exchanger and CDU wetted construction around customer-approved material requirements. We do not treat a material grade, corrosion-resistance statement or certification as confirmed until it is included in the project specification and supported by the applicable manufacturing and inspection documentation.
The following table is a reference framework for early project discussion, not a confirmed product datasheet. Actual values must be calculated and approved for the specific GPU cluster.
Engineering item | Typical or illustrative reference | Final confirmation required |
|---|---|---|
CDU thermal capacity | Approximately 50 kW to 1,500 kW per module; larger systems may use multiple modules | Rack heat load, diversity and future expansion |
Secondary supply temperature | Project-defined range; often selected within a moderate liquid-cooling temperature band | Server, cold-plate and facility-water requirements |
Secondary return temperature | Project-defined according to rack heat pickup | Heat balance and control strategy |
Secondary coolant flow | Approximately 5 to 300 m³/h for selected module ranges | Heat load, temperature rise and pressure-drop calculation |
Facility-water flow | Calculated independently from facility-water temperature rise | Facility-water design and plant limitations |
Secondary-side design pressure | Often engineered within a project range such as 6 to 16 bar | Piping class, cold-plate rating and relief design |
Heat exchanger material | Stainless steel, titanium or other approved construction | Coolant chemistry and corrosion review |
Pump arrangement | Single, duty/standby or parallel variable-speed pumps | Availability target and maintenance philosophy |
Filtration | Customer-defined strainer or filter grade | Cold-plate and valve particle tolerance |
Electrical supply | Common industrial AC supply; other options may be engineered | Site power and control-panel specification |
Communication | Modbus, BACnet, dry contacts or customer protocol | BMS/DCIM point list |
Enclosure arrangement | Indoor technical room, in-row, rack-side or packaged skid | Access, floor loading and environmental conditions |
These values should not be used for procurement, server acceptance or construction release without a complete selection calculation.
A sound CDU selection begins with a complete heat and flow balance.
Define the connected GPU, CPU, memory, networking and power-conversion heat load. Separate present load from future expansion and identify whether the stated value is nameplate load, measured load, design load or diversified load.
The secondary supply and return temperatures determine the required flow for a given heat load. In simplified form:
Heat load ≈ mass flow × specific heat × temperature rise The actual calculation should use the selected coolant properties at the operating temperature and the project’s approved unit system.
Include pressure losses through:
CDU heat exchanger.
Pump and control valves.
Filters and strainers.
Main headers and branch piping.
Rack manifolds.
Quick disconnects and flexible hoses.
GPU cold plates and server distribution blocks.
The facility-water and secondary-loop temperatures must provide an adequate heat-transfer driving force. A smaller approach can reduce heat-exchanger size but may increase area, flow, cost and sensitivity to fouling.
Decide whether redundancy applies to pumps, heat exchangers, control power, sensors, CDU modules, facility-water branches or complete cooling paths. A redundant pump alone does not create a fully redundant cooling system if the heat exchanger, power source or upstream facility loop remains a single point of failure.
Review startup, rack ramp-up, pump switching, emergency shutdown, loss of facility water, loss of electrical power and rapid GPU load changes. The CDU controls and thermal mass should be evaluated against the project’s transient requirements.
GPU cluster loads can change rapidly during training, inference, rendering, simulation and batch scheduling. A CDU should therefore be integrated as a controllable subsystem rather than treated as a fixed-speed pump skid.
The controller monitors supply temperature, return temperature, flow and differential pressure. It adjusts pump speed or valve position to maintain the configured operating point.
At reduced IT load, pump speed can be reduced within the permitted flow range. The control strategy must preserve minimum flow requirements for the cold plates and avoid unstable valve hunting.
When the return temperature or differential pressure rises, the CDU can increase flow, request additional facility-water capacity or issue a supervisory alarm. The exact sequence depends on the data center control architecture.
For a duty/standby design, the controller can identify a pump fault and start the standby pump if the project permits automatic changeover. The changeover sequence, alarm delay and operator notification must be specified during controls engineering.
The CDU should provide configurable alarms for high supply temperature, high return temperature, low flow, high differential pressure, filter blockage, sensor failure and communication loss. Alarm thresholds must be set using the equipment limits, not generic values.
Hyperscale facilities evaluate CDU reliability at the system level. The following design questions should be answered before release:
Can pumps be isolated and replaced without draining the complete secondary loop?
Can filters be serviced without exposing the loop to uncontrolled contamination?
Are the heat exchanger and piping accessible for inspection and cleaning?
Is there a controlled filling, draining and air-removal procedure?
Are leak sensors tested and replaceable?
Is there a local manual override for commissioning?
Are critical sensors duplicated where the project requires it?
Can the CDU operate safely during BMS communication loss?
Are spare pumps, seals, cartridges and sensors available?
Does the skid fit through the planned doors, lifts and maintenance routes?
CSTHEATEXCHANGER can configure the CDU around the customer’s service philosophy, but final maintainability depends on the installation layout and the complete cooling-loop design.
The CDU supplies coolant to cold plates mounted on GPUs, CPUs or other high-power devices. The design must coordinate coolant cleanliness, flow balance, pressure limits, connector design and rack manifold layout.
A CDU can supply a secondary loop to rear-door heat exchangers that remove heat from server exhaust air. This application may require a different temperature range and flow distribution than direct-to-chip cooling.
Some data halls contain both direct-to-chip racks and rear-door heat exchangers. The CDU system may require separate branches, independent control valves or multiple temperature zones.
HPC clusters may combine CPU cold plates, GPU cold plates, memory cooling and high-flow rack manifolds. The CDU should be selected using the combined pressure-drop curve and expected workload profile.
For a phased hyperscale build, modular CDUs can be added as rack blocks are commissioned. The expansion plan should reserve hydraulic, electrical, controls and maintenance capacity from the first construction phase.
A liquid-to-liquid CDU is a controlled heat-transfer and coolant-distribution package. It transfers heat from a secondary liquid loop serving liquid-cooled IT equipment to a facility-water loop through a heat exchanger, while managing circulation, temperature, pressure, filtration and alarms.
A CDU can isolate the IT equipment from facility-water chemistry and pressure conditions. It also allows the secondary loop to use a separately controlled coolant, filtration arrangement and pump curve. Whether a CDU is required depends on the server supplier, facility design, warranty conditions and project risk assessment.
Yes, a CDU can serve multiple racks when its heat-transfer capacity, flow range, pressure capability, manifold arrangement and control system are designed for the complete connected load. Rack diversity and future expansion must be included in the selection calculation.
Plate heat exchangers are commonly considered for compact high-density applications, while shell-and-tube or other constructions may be selected for specific fluid, pressure, serviceability or material requirements. The final choice depends on the actual project conditions.
Not necessarily. Some systems use treated water, while others use inhibited ethylene glycol, propylene glycol or a project-specific coolant. The correct fluid depends on freeze protection, chemistry, equipment requirements and facility operating conditions.
The minimum selection package normally includes total and per-rack heat load, current and future rack quantity, secondary coolant, supply and return temperatures, required flow, allowable pressure drop, facility-water conditions, redundancy philosophy, power supply, controls protocol, installation location and maintenance constraints.
Yes. We can develop the liquid-to-liquid heat exchanger, pump arrangement, filtration, controls, piping interfaces, enclosure and monitoring functions around the customer’s project specification. Final performance and compliance remain subject to engineering calculation, drawing review, material confirmation and acceptance testing.
Please provide the following information for a project-specific CDU proposal:
1. Application:
Hyperscale GPU cluster, AI training hall, HPC, inference cluster or mixed liquid cooling
2. Thermal load:
Total present load, future load, per-rack load and required diversity factor
3. Rack information:
Rack quantity, rack density, cold-plate type, manifold type and quick-disconnect specification
4. Secondary loop:
Coolant type, concentration, conductivity, pH, allowable contamination and temperature limits
5. Secondary temperatures:
Required supply temperature, return temperature and allowable transient range
6. Flow and pressure:
Required minimum/normal/maximum flow and allowable pressure drop at the CDU boundary
7. Facility-water side:
Inlet temperature, return temperature, flow availability, pressure range, water chemistry and filtration
8. Heat exchanger requirements:
Preferred construction, wetted materials, inspection requirements and service method
9. Redundancy:
Pump redundancy, heat-exchanger redundancy, control-power redundancy and desired failure-domain separation
10. Electrical supply:
Voltage, phase, frequency, dual-power requirement and upstream protection
11. Controls and monitoring:
Local HMI, Modbus RTU/TCP, BACnet, dry contacts, DCIM point list and alarm priorities
12. Mechanical interfaces:
Footprint, height, weight limit, lifting points, piping connections, access route and maintenance clearance
13. Environmental conditions:
Indoor ambient range, humidity, seismic requirements, acoustic limits and installation elevation
14. Acceptance requirements:
Factory test plan, pressure test, leak test, performance test, FAT documentation and site commissioning scope CSTHEATEXCHANGER develops engineered liquid-to-liquid CDU systems for high-density GPU and HPC cooling applications, including:
Liquid-to-liquid heat exchanger selection for facility and secondary coolant loops.
Pump packages for rack-level, row-level or modular CDU architectures.
Filtration, air management, expansion and drain/fill assemblies.
Temperature, flow and differential-pressure control.
Leak detection, pump-failure alarms and BMS/DCIM communication.
Stainless steel, titanium or other project-approved wetted constructions.
Custom piping connections, skid frames, enclosures and maintenance access.
Factory inspection and testing based on the agreed project specification.
Send us your GPU cluster heat load, rack arrangement, coolant chemistry, temperature targets, facility-water conditions and control requirements. We will review the hydraulic and thermal boundary conditions before preparing a project-specific CDU concept and selection proposal.