At CSTHEATEXCHANGER, we design and manufacture high-efficiency Coolant Distribution Units (CDU) specifically engineered for direct-to-chip (DTC) cold plate loops, single-phase immersion cooling tanks, high-density AI/GPU computing clusters, and hyperscale cloud data centers (thermal cooling distribution capacities scaled from 50 kW to over 1,500 kW, operating across primary loop supply water temperatures of +15∘C to +32∘C and secondary electronic coolant delivery temperatures of +30∘C to +45∘C, achieving annualized PUE<1.05–1.10). Available in In-Rack 4U/8U/12U modular units, In-Row footprint cabinets, and Centralized Floor-Standing / Containerized CDU Skids, CST CDUs integrate corrugated AISI 316L/Titanium brazed plate heat exchangers, dual N+1 redundant canned-motor/VFD stainless steel circulating pumps, intelligent PLC touchscreens with Modbus/BACnet telemetry, precision 5-micron particle filtration, and automated expansion de-aeration systems, providing 100% hydraulic isolation between facility water and IT cold plates, zero cross-contamination, and continuous 24/7/365 mission-critical thermal stability.
In modern high-density data centers where server rack power densities exceed 30 kW to 100+ kW30 kW to 100+ kW, facility raw water cannot be circulated directly into sensitive server cold plates due to contamination, scaling, and pressure surge risks. The CST Coolant Distribution Unit (CDU) serves as the critical hydraulic isolation and thermal exchange bridge:
DATA CENTER CDU DUAL-LOOP HYDRAULIC & THERMAL ARCHITECTURE
======================= PRIMARY FACILITY WATER LOOP (FWS) =======================
(Chilled Water Plant, Outdoor Closed-Circuit Adiabatic Dry Cooler, or Cooling Tower)
┌───────────────────────────────────────────────────────────────────────────────┐
│ Facility Supply Water (+15°C to +30°C) ──► [PRIMARY WATER INLET] │
└──────────────────────────────────────┬────────────────────────────────────────┘
│
▼
┌───────────────────────────────────────────────────────────────────────────────┐
│ [CST INDUSTRIAL COOLANT DISTRIBUTION UNIT (CDU)] │
│ • Heavy AISI 316L / Titanium Brazed Plate Heat Exchanger (Close ΔT ≤ 1.5–2.0K)│
│ • Dual N+1 Stainless Steel VFD / Inverter Magnetic Drive Circulation Pumps │
│ • Integrated 5 µm Bag Filter + Magnetic Ferrous Particle Trap │
│ • Automated Closed Diaphragm Expansion Tank & Electronic De-aeration Vessel │
│ • Intelligent PLC Controller with Dual Power Feeds (ATS) & Leak Sensors │
└──────────────────────────────────────┬────────────────────────────────────────┘
│
▼
======================= SECONDARY TECHNOLOGY COOLING LOOP (TCS) ================
(Treated Deionized Water, Inhibited Propylene Glycol, or Dielectric Coolant)
┌───────────────────────────────────────────────────────────────────────────────┐
│ [HIGH-DENSITY COMPUTE RACKS / DIRECT-TO-CHIP COLD PLATES / IMMERSION TANKS] │
│ • Supplies +35°C to +45°C Ultra-Pure Liquid Directly to GPU & CPU Cold Plates │
│ • Returns +55°C to +65°C Heated Coolant Back to CDU with Zero Contamination │
└───────────────────────────────────────────────────────────────────────────────┘ ================================================================================
CST PRECISION LIQUID-TO-LIQUID CDU VS. DIRECT FACILITY WATER CONNECTION
================================================================================
Evaluation Metric CST Coolant Distribution Unit (CDU)Direct Facility Chilled Water Hookup
--------------------------------------------------------------------------------
Hydraulic Loop Isolation 100% Physical Isolation (BPHE) Zero Isolation (Facility water enters chips)
Cold Plate Scaling & Clogging Zero Scaling (Dedicated pure fluid)Severe scaling & particle clogging
Pressure Surge Protection Maintains stable 0.15–0.25 MPa loopSubject to massive building pressure spikes
Pump Redundancy Architecture Dual N+1 Automated VFD Pump Skid Single point of failure on main plant pump
Filtration & Fluid Cleanliness Continuous 5 µm + Magnetic Filter Raw facility debris fouls micro-channels
Fluid Chemistry Management Controlled Deionized/Inhibited GlycolRaw water chemistry degrades cold plates
Leak Detection & Containment Multi-zone optical sensors & shutoffUncontrolled water flooding in server rack
Annualized System PUE Impact Ultra-Low PUE 1.05 to 1.10 Higher pumping losses & thermal bypassing
================================================================================ Facility cooling loops operate at high static pressures (often >0.6–1.0 MPa>0.6–1.0 MPa) and contain particulate debris. CST CDUs isolate the secondary Technology Cooling System (TCS) loop via all-brazed AISI 316L plate heat exchangers, maintaining a controlled, low-pressure (0.15–0.25 MPa0.15–0.25 MPa), steady flow across server cold plates to prevent hose ruptures and mechanical joint weeping.
Mission-critical AI computing cannot tolerate flow interruptions. Every CST CDU incorporates dual stainless steel variable-frequency drive (VFD) circulation pumps operating in active N+1 redundancy. If a primary pump encounters an electrical fault, the intelligent PLC triggers sub-second automatic failover without server thermal throttling or flow cavitation.
CSTHEATEXCHANGER manufactures all data center CDUs under strict ISO 9001:2015 and cleanroom assembly standards:
CST DATA CENTER CDU SUBSYSTEM METALLURGY
┌─────────────────────────────────────────────────────────────────────────┐
│ [1. BASE HEAT EXCHANGER MATRIX] │
│ • Vacuum-Brazed AISI 316L Stainless Steel / Titanium Plates. │
│ • High-Theta Herringbone Corrugation for tight approach (ΔT ≤ 1.5 K). │
├─────────────────────────────────────────────────────────────────────────┤
│ [2. CIRCULATING PUMPS & HYDRAULIC PIPING] │
│ • Dual Canned-Motor / Magnetic Drive Inverter Pumps (Zero Seal Leaks). │
│ • Fully Passivated 304/316L Stainless Steel Internal Manifolds & Valves.│
├─────────────────────────────────────────────────────────────────────────┤
│ [3. PURIFICATION, FILTRATION & EXPANSION] │
│ • Dual 5-Micron Cleanable Stainless Bag Filters with dP Differential Mon.│
│ • Integrated Diaphragm Expansion Vessel & Automatic Air Vent Separator. │
└─────────────────────────────────────────────────────────────────────────┘ CST DATA CENTER CDU MANUFACTURING & TESTING GATES
FROM CERTIFIED SANITARY STAINLESS STEEL PIPING & VACUUM BRAZED HEAT EXCHANGERS
┌─────────────────────────────────────────────────────────────────────────┐
│ [ STAGE 1: ORBITAL TIG WELDING & CLEANROOM PIPING PASSIVATION ] │
│ 100% inert gas back-purged welds; pickling removes internal scale │
├─────────────────────────────────────────────────────────────────────────┤
│ [ STAGE 2: HYDROSTATIC PROOF TESTING (1.6 MPa / 16 BAR) ] │
│ Proof tested at 1.5x design pressure across primary and secondary loops │
├─────────────────────────────────────────────────────────────────────────┤
│ [ STAGE 3: HELIUM MASS SPECTROMETER VACUUM LEAK TESTING ] │
│ Certified zero-leak joint integrity (Leak rate < 1x10⁻⁶ mbar·L/s) │
├─────────────────────────────────────────────────────────────────────────┤
│ [ STAGE 4: FULL-LOAD THERMAL RUN & REDUNDANT FAILOVER FAT ] │
│ Multi-point sensor calibration and simulated N+1 pump trip verification │
└─────────────────────────────────────────────────────────────────────────┘
DELIVERS MAXIMUM LIQUID COOLING UPTIME & ZERO LEAK RELIABILITY To maximize the number of hours per year that the data center can operate in 100%100% free-cooling dry cooler mode without running energy-intensive mechanical chillers, CST designs CDUs with ultra-high surface area brazed plate heat exchangers, achieving thermal approaches down to ΔT≤1.5 KΔT≤1.5 K between facility water and server coolant.
To safeguard high-value compute hardware, CST CDUs feature multi-point optical leak rope sensors along the cabinet drip tray and external rack manifolds. Upon sensing conductive fluid, the PLC immediately alerts the central DCIM via Modbus/SNMP and can be configured to instantly modulate or shut off secondary flow to contain fluid release.
CSTHEATEXCHANGER COOLANT DISTRIBUTION UNIT PORTFOLIO
[1. IN-RACK MODULAR CDUs (CST-CDU-RACK SERIES)]
• Capacity: 40 kW to 120 kW; Form Factor: 4U / 6U / 8U / 12U Standard 19" Rack Mount.
• Ideal for individual high-density compute racks, edge AI pods, and prototype liquid cooling labs.
─────────────────────────────────────────────────────────────────────────────
[2. IN-ROW MODULAR CABINET CDUs (CST-CDU-ROW SERIES)]
• Capacity: 150 kW to 400 kW; Form Factor: 300 mm or 600 mm In-Row Cabinet Enclosure.
• Sized for row-based Direct-to-Chip clusters, enterprise server suites, and high-density GPU rows.
─────────────────────────────────────────────────────────────────────────────
[3. CENTRALIZED FLOOR-STANDING / SKID CDUs (CST-CDU-MAX SERIES)]
• Capacity: 500 kW to 1,500+ kW; Form Factor: Standalone Floor Skid or Prefab Container Subsystem.
• Engineered for multi-megawatt hyperscale data center facilities and centralized pump rooms. (Note: The following engineering parameters represent standard manufacturing design envelopes. Cooling capacities, pump flow rates, manifold port sizes, and electrical voltages are 100% custom-tailored to client server rack layouts and MEP blueprints.)
================================================================================
CST DATA CENTER COOLANT DISTRIBUTION UNIT (CST-CDU-SERIES)
================================================================================
Engineering Parameter Standard Manufacturing & Design Range
--------------------------------------------------------------------------------
Nominal Heat Exchange Capacity 50 kW to 1,500+ kW (170,000 to 5,100,000+ BTU/h)
Form Factor Configurations In-Rack (4U–12U), In-Row (300/600 mm), Floor-Standing Skid
Primary Loop Fluid CompatibilityClean Facility Water, Chilled Water, 20%–35% Glycol-Water
Secondary Loop Fluid Media Deionized Water, Inhibited Propylene Glycol, Dielectric Oil
Secondary Fluid Flow Capacity 3.0 m³/h to 180+ m³/h (13 to 790+ GPM)
Primary Supply Water Temperature+15°C to +32°C (+59°F to +89.6°F)
Secondary Supply Temperature +30°C to +45°C (+86°F to +113°F) Precision Controlled
Thermal Approach Capability (ΔT)Tight Approach: ΔT ≤ 1.5 K to 2.0 K (Fluid-to-Fluid)
Pumping Architecture Dual N+1 Redundant Canned-Motor / Magnetic Drive VFD Pumps
Filtration Specification 5 µm Stainless Cleanable Bag Filter + Magnetic Iron Trap
Internal Piping Metallurgy AISI 304 / 316L Sanitary Stainless Steel (Full Passivation)
Heat Exchanger Plate Metallurgy AISI 316L Stainless Steel / Grade 2 Titanium (Vacuum Brazed)
Design Operating Pressure Range Primary: Up to 1.6 MPa (16 bar); Secondary: Up to 1.0 MPa (10 bar)
Hydrostatic Proof Test Pressure 1.6 MPa to 2.4 MPa (16 to 24 bar / 232–348 psi)
Power Supply Options 208V / 230V 1-Phase, 380V / 400V / 480V 3-Phase (50/60 Hz)
Electrical Redundancy Standard Dual Power Feeds with Integrated Automatic Transfer Switch (ATS)
Control & Telemetry Interface 7" or 10" Color Touchscreen PLC, Modbus-TCP/RTU, SNMP v3, BACnet
Quality Standards & Compliance CE Compliant, ISO 9001:2015, TIA-942 Ready, UL 60950/62368
Testing & Quality Assurance 100% Helium Mass Spectrometer Testing + Full-Load FAT Pre-Test
================================================================================ A CDU acts as the thermal and hydraulic separation barrier between raw facility water and delicate server electronics. It precisely regulates secondary coolant flow, temperature, and pressure (0.15–0.25 MPa0.15–0.25 MPa), provides continuous 5 μm5 μm filtration, and prevents facility water contamination and pressure spikes from damaging cold plates.
An In-Rack CDU (4U–12U) mounts inside a standard 19-inch IT rack to cool that specific rack (40–120 kW40–120 kW), ideal for edge pods. An In-Row or Centralized Floor CDU (150–1,500+ kW150–1,500+ kW) is a standalone unit that distributes conditioned coolant to an entire row of 6 to 20 server racks through overhead or underfloor stainless steel supply headers.
CST utilizes high-efficiency vacuum-brazed AISI 316L plate heat exchangers with high-theta corrugation patterns, achieving fluid-to-fluid temperature approaches as tight as ΔT≤1.5–2.0 K. This allows the facility to reject heat directly using outdoor dry coolers for most of the year without running mechanical chillers, driving annualized PUE below 1.081.08.
Maximize data center liquid cooling uptime, protect sensitive server cold plates, and achieve industry-leading PUE (<1.08<1.08) with CSTHEATEXCHANGER:
Custom Coolant Distribution Units (CDU) from 50 kW to 1,500 kW+
In-Rack (4U–12U), In-Row Cabinets & Centralized Floor-Standing CDUs
Dual N+1 Redundant Magnetic/Canned-Motor Inverter Pumps with Sub-Second Failover
Corrugated AISI 316L / Titanium Brazed Plate Heat Exchangers (Close ΔT≤1.5 KΔT≤1.5 K)
Integrated 5 μm5 μm Filtration, Automatic Expansion Tanks & Multi-Zone Leak Detection
Full CE / ISO 9001:2015 Compliance, 100%100% Factory Tested & Global Direct Delivery
Contact our specialized mission-critical data center liquid cooling engineering team today with your server rack power loads (kW), primary/secondary temperature targets, and facility layout for custom 3D CAD modeling proposals and factory-direct quotations.
Website: https://www.cstheatexchanger.com/
Technical Inquiries: info@cstheatexchanger.com
Coolant Distribution Unit (CDU) for Data Center Cooling | CST
Stainless Steel Cold Room Evaporator for Sausage Storage | CST
Wall Monoblock Unit for Fresh Meat Storage (+1°C to +6°C) | CST
Hot Water Air Heating Coils for Firewood Drying Chambers | CST
Carbonization Furnace Flue Gas Heat Exchanger for Wood Drying | CST
International Business:+86 0519 8878 2189
Domestic business:+86 0519 8878 2190