Coolant Distribution Unit (CDU) for Data Center Cooling | CST

Views: 0     Author: Site Editor     Publish Time: 2026-11-17      Origin: Site

At CSTHEATEXCHANGER, we design and manufacture high-efficiency Coolant Distribution Units (CDU) specifically engineered for direct-to-chip (DTC) cold plate loops, single-phase immersion cooling tanks, high-density AI/GPU computing clusters, and hyperscale cloud data centers (thermal cooling distribution capacities scaled from 50 kW to over 1,500 kW, operating across primary loop supply water temperatures of +15∘C to +32∘C and secondary electronic coolant delivery temperatures of +30∘C to +45∘C, achieving annualized PUE<1.05–1.10). Available in In-Rack 4U/8U/12U modular units, In-Row footprint cabinets, and Centralized Floor-Standing / Containerized CDU Skids, CST CDUs integrate corrugated AISI 316L/Titanium brazed plate heat exchangers, dual N+1 redundant canned-motor/VFD stainless steel circulating pumps, intelligent PLC touchscreens with Modbus/BACnet telemetry, precision 5-micron particle filtration, and automated expansion de-aeration systems, providing 100% hydraulic isolation between facility water and IT cold plates, zero cross-contamination, and continuous 24/7/365 mission-critical thermal stability.

CSTHEATEXCHANGER Coolant Distribution Units (CDU) for High-Density Data Center Liquid Cooling.jpg

1. Thermodynamic & Hydraulic Architecture: The Central Role of CDUs in Liquid Cooling

In modern high-density data centers where server rack power densities exceed 30 kW to 100+ kW30 kW to 100+ kW, facility raw water cannot be circulated directly into sensitive server cold plates due to contamination, scaling, and pressure surge risks. The CST Coolant Distribution Unit (CDU) serves as the critical hydraulic isolation and thermal exchange bridge:

        DATA CENTER CDU DUAL-LOOP HYDRAULIC & THERMAL ARCHITECTURE
        
   ======================= PRIMARY FACILITY WATER LOOP (FWS) =======================
   (Chilled Water Plant, Outdoor Closed-Circuit Adiabatic Dry Cooler, or Cooling Tower)
   ┌───────────────────────────────────────────────────────────────────────────────┐
   │ Facility Supply Water (+15°C to +30°C) ──► [PRIMARY WATER INLET]              │
   └──────────────────────────────────────┬────────────────────────────────────────┘
                                          │
                                          ▼
   ┌───────────────────────────────────────────────────────────────────────────────┐
   │ [CST INDUSTRIAL COOLANT DISTRIBUTION UNIT (CDU)]                              │
   │ • Heavy AISI 316L / Titanium Brazed Plate Heat Exchanger (Close ΔT ≤ 1.5–2.0K)│
   │ • Dual N+1 Stainless Steel VFD / Inverter Magnetic Drive Circulation Pumps   │
   │ • Integrated 5 µm Bag Filter + Magnetic Ferrous Particle Trap                │
   │ • Automated Closed Diaphragm Expansion Tank & Electronic De-aeration Vessel   │
   │ • Intelligent PLC Controller with Dual Power Feeds (ATS) & Leak Sensors      │
   └──────────────────────────────────────┬────────────────────────────────────────┘
                                          │
                                          ▼
   ======================= SECONDARY TECHNOLOGY COOLING LOOP (TCS) ================
   (Treated Deionized Water, Inhibited Propylene Glycol, or Dielectric Coolant)
   ┌───────────────────────────────────────────────────────────────────────────────┐
   │ [HIGH-DENSITY COMPUTE RACKS / DIRECT-TO-CHIP COLD PLATES / IMMERSION TANKS]   │
   │ • Supplies +35°C to +45°C Ultra-Pure Liquid Directly to GPU & CPU Cold Plates │
   │ • Returns +55°C to +65°C Heated Coolant Back to CDU with Zero Contamination   │
   └───────────────────────────────────────────────────────────────────────────────┘
================================================================================
CST PRECISION LIQUID-TO-LIQUID CDU VS. DIRECT FACILITY WATER CONNECTION
================================================================================
Evaluation Metric              CST Coolant Distribution Unit (CDU)Direct Facility Chilled Water Hookup
--------------------------------------------------------------------------------
Hydraulic Loop Isolation       100% Physical Isolation (BPHE)   Zero Isolation (Facility water enters chips)
Cold Plate Scaling & Clogging  Zero Scaling (Dedicated pure fluid)Severe scaling & particle clogging
Pressure Surge Protection      Maintains stable 0.15–0.25 MPa loopSubject to massive building pressure spikes
Pump Redundancy Architecture   Dual N+1 Automated VFD Pump Skid Single point of failure on main plant pump
Filtration & Fluid Cleanliness Continuous 5 µm + Magnetic Filter Raw facility debris fouls micro-channels
Fluid Chemistry Management     Controlled Deionized/Inhibited GlycolRaw water chemistry degrades cold plates
Leak Detection & Containment   Multi-zone optical sensors & shutoffUncontrolled water flooding in server rack
Annualized System PUE Impact   Ultra-Low PUE 1.05 to 1.10       Higher pumping losses & thermal bypassing
================================================================================

1. 100% Hydraulic Isolation & Constant Secondary Pressure Regulation

Facility cooling loops operate at high static pressures (often >0.6–1.0 MPa>0.6–1.0 MPa) and contain particulate debris. CST CDUs isolate the secondary Technology Cooling System (TCS) loop via all-brazed AISI 316L plate heat exchangers, maintaining a controlled, low-pressure (0.15–0.25 MPa0.15–0.25 MPa), steady flow across server cold plates to prevent hose ruptures and mechanical joint weeping.

2. Dual N+1 Redundant Pumping with Sub-Second Automatic Failover

Mission-critical AI computing cannot tolerate flow interruptions. Every CST CDU incorporates dual stainless steel variable-frequency drive (VFD) circulation pumps operating in active N+1 redundancy. If a primary pump encounters an electrical fault, the intelligent PLC triggers sub-second automatic failover without server thermal throttling or flow cavitation.

2. Metallurgy & Manufacturing Engineering: Quality Assurance & Subsystem Integration

CSTHEATEXCHANGER manufactures all data center CDUs under strict ISO 9001:2015 and cleanroom assembly standards:

        CST DATA CENTER CDU SUBSYSTEM METALLURGY
        
   ┌─────────────────────────────────────────────────────────────────────────┐
   │ [1. BASE HEAT EXCHANGER MATRIX]                                         │
   │ • Vacuum-Brazed AISI 316L Stainless Steel / Titanium Plates.            │
   │ • High-Theta Herringbone Corrugation for tight approach (ΔT ≤ 1.5 K).   │
   ├─────────────────────────────────────────────────────────────────────────┤
   │ [2. CIRCULATING PUMPS & HYDRAULIC PIPING]                               │
   │ • Dual Canned-Motor / Magnetic Drive Inverter Pumps (Zero Seal Leaks).  │
   │ • Fully Passivated 304/316L Stainless Steel Internal Manifolds & Valves.│
   ├─────────────────────────────────────────────────────────────────────────┤
   │ [3. PURIFICATION, FILTRATION & EXPANSION]                               │
   │ • Dual 5-Micron Cleanable Stainless Bag Filters with dP Differential Mon.│
   │ • Integrated Diaphragm Expansion Vessel & Automatic Air Vent Separator. │
   └─────────────────────────────────────────────────────────────────────────┘
       CST DATA CENTER CDU MANUFACTURING & TESTING GATES
       
   FROM CERTIFIED SANITARY STAINLESS STEEL PIPING & VACUUM BRAZED HEAT EXCHANGERS
   ┌─────────────────────────────────────────────────────────────────────────┐
   │ [ STAGE 1: ORBITAL TIG WELDING & CLEANROOM PIPING PASSIVATION ]         │
   │ 100% inert gas back-purged welds; pickling removes internal scale       │
   ├─────────────────────────────────────────────────────────────────────────┤
   │ [ STAGE 2: HYDROSTATIC PROOF TESTING (1.6 MPa / 16 BAR) ]               │
   │ Proof tested at 1.5x design pressure across primary and secondary loops │
   ├─────────────────────────────────────────────────────────────────────────┤
   │ [ STAGE 3: HELIUM MASS SPECTROMETER VACUUM LEAK TESTING ]               │
   │ Certified zero-leak joint integrity (Leak rate < 1x10⁻⁶ mbar·L/s)        │
   ├─────────────────────────────────────────────────────────────────────────┤
   │ [ STAGE 4: FULL-LOAD THERMAL RUN & REDUNDANT FAILOVER FAT ]             │
   │ Multi-point sensor calibration and simulated N+1 pump trip verification │
   └─────────────────────────────────────────────────────────────────────────┘
   DELIVERS MAXIMUM LIQUID COOLING UPTIME & ZERO LEAK RELIABILITY

1. Close Approach Temperature (ΔT≤1.5–2.0 KΔT≤1.5–2.0 K)

To maximize the number of hours per year that the data center can operate in 100%100% free-cooling dry cooler mode without running energy-intensive mechanical chillers, CST designs CDUs with ultra-high surface area brazed plate heat exchangers, achieving thermal approaches down to ΔT≤1.5 KΔT≤1.5 K between facility water and server coolant.

2. Multi-Zone Optical Leak Detection & Automatic Emergency Isolation

To safeguard high-value compute hardware, CST CDUs feature multi-point optical leak rope sensors along the cabinet drip tray and external rack manifolds. Upon sensing conductive fluid, the PLC immediately alerts the central DCIM via Modbus/SNMP and can be configured to instantly modulate or shut off secondary flow to contain fluid release.

3. Product Configurations: In-Rack, In-Row & Floor-Standing CDU Series

        CSTHEATEXCHANGER COOLANT DISTRIBUTION UNIT PORTFOLIO
        
   [1. IN-RACK MODULAR CDUs (CST-CDU-RACK SERIES)]
   • Capacity: 40 kW to 120 kW; Form Factor: 4U / 6U / 8U / 12U Standard 19" Rack Mount.
   • Ideal for individual high-density compute racks, edge AI pods, and prototype liquid cooling labs.
   ─────────────────────────────────────────────────────────────────────────────
   [2. IN-ROW MODULAR CABINET CDUs (CST-CDU-ROW SERIES)]
   • Capacity: 150 kW to 400 kW; Form Factor: 300 mm or 600 mm In-Row Cabinet Enclosure.
   • Sized for row-based Direct-to-Chip clusters, enterprise server suites, and high-density GPU rows.
   ─────────────────────────────────────────────────────────────────────────────
   [3. CENTRALIZED FLOOR-STANDING / SKID CDUs (CST-CDU-MAX SERIES)]
   • Capacity: 500 kW to 1,500+ kW; Form Factor: Standalone Floor Skid or Prefab Container Subsystem.
   • Engineered for multi-megawatt hyperscale data center facilities and centralized pump rooms.

4. Technical Specifications — Data Center Coolant Distribution Units

(Note: The following engineering parameters represent standard manufacturing design envelopes. Cooling capacities, pump flow rates, manifold port sizes, and electrical voltages are 100% custom-tailored to client server rack layouts and MEP blueprints.)

================================================================================
CST DATA CENTER COOLANT DISTRIBUTION UNIT (CST-CDU-SERIES)
================================================================================
Engineering Parameter           Standard Manufacturing & Design Range
--------------------------------------------------------------------------------
Nominal Heat Exchange Capacity  50 kW to 1,500+ kW (170,000 to 5,100,000+ BTU/h)
Form Factor Configurations      In-Rack (4U–12U), In-Row (300/600 mm), Floor-Standing Skid
Primary Loop Fluid CompatibilityClean Facility Water, Chilled Water, 20%–35% Glycol-Water
Secondary Loop Fluid Media      Deionized Water, Inhibited Propylene Glycol, Dielectric Oil
Secondary Fluid Flow Capacity   3.0 m³/h to 180+ m³/h (13 to 790+ GPM)
Primary Supply Water Temperature+15°C to +32°C (+59°F to +89.6°F)
Secondary Supply Temperature    +30°C to +45°C (+86°F to +113°F) Precision Controlled
Thermal Approach Capability (ΔT)Tight Approach: ΔT ≤ 1.5 K to 2.0 K (Fluid-to-Fluid)
Pumping Architecture           Dual N+1 Redundant Canned-Motor / Magnetic Drive VFD Pumps
Filtration Specification        5 µm Stainless Cleanable Bag Filter + Magnetic Iron Trap
Internal Piping Metallurgy      AISI 304 / 316L Sanitary Stainless Steel (Full Passivation)
Heat Exchanger Plate Metallurgy AISI 316L Stainless Steel / Grade 2 Titanium (Vacuum Brazed)
Design Operating Pressure Range Primary: Up to 1.6 MPa (16 bar); Secondary: Up to 1.0 MPa (10 bar)
Hydrostatic Proof Test Pressure 1.6 MPa to 2.4 MPa (16 to 24 bar / 232–348 psi)
Power Supply Options            208V / 230V 1-Phase, 380V / 400V / 480V 3-Phase (50/60 Hz)
Electrical Redundancy Standard  Dual Power Feeds with Integrated Automatic Transfer Switch (ATS)
Control & Telemetry Interface   7" or 10" Color Touchscreen PLC, Modbus-TCP/RTU, SNMP v3, BACnet
Quality Standards & Compliance  CE Compliant, ISO 9001:2015, TIA-942 Ready, UL 60950/62368
Testing & Quality Assurance     100% Helium Mass Spectrometer Testing + Full-Load FAT Pre-Test
================================================================================

5. Frequently Asked Questions (FAQ)

What is the primary purpose of a Coolant Distribution Unit (CDU) in data center liquid cooling?

A CDU acts as the thermal and hydraulic separation barrier between raw facility water and delicate server electronics. It precisely regulates secondary coolant flow, temperature, and pressure (0.15–0.25 MPa0.15–0.25 MPa), provides continuous 5 μm5 μm filtration, and prevents facility water contamination and pressure spikes from damaging cold plates.

What is the difference between an In-Rack CDU and an In-Row / Centralized CDU?

An In-Rack CDU (4U–12U) mounts inside a standard 19-inch IT rack to cool that specific rack (40–120 kW40–120 kW), ideal for edge pods. An In-Row or Centralized Floor CDU (150–1,500+ kW150–1,500+ kW) is a standalone unit that distributes conditioned coolant to an entire row of 6 to 20 server racks through overhead or underfloor stainless steel supply headers.

How does the CDU maintain close temperature approach (ΔTΔT) to enable free cooling?

CST utilizes high-efficiency vacuum-brazed AISI 316L plate heat exchangers with high-theta corrugation patterns, achieving fluid-to-fluid temperature approaches as tight as ΔT≤1.5–2.0 K. This allows the facility to reject heat directly using outdoor dry coolers for most of the year without running mechanical chillers, driving annualized PUE below 1.081.08.

Source Custom Coolant Distribution Units (CDU) from CSTHEATEXCHANGER

Maximize data center liquid cooling uptime, protect sensitive server cold plates, and achieve industry-leading PUE (<1.08<1.08) with CSTHEATEXCHANGER:

  • Custom Coolant Distribution Units (CDU) from 50 kW to 1,500 kW+

  • In-Rack (4U–12U), In-Row Cabinets & Centralized Floor-Standing CDUs

  • Dual N+1 Redundant Magnetic/Canned-Motor Inverter Pumps with Sub-Second Failover

  • Corrugated AISI 316L / Titanium Brazed Plate Heat Exchangers (Close ΔT≤1.5 KΔT≤1.5 K)

  • Integrated 5 μm5 μm Filtration, Automatic Expansion Tanks & Multi-Zone Leak Detection

  • Full CE / ISO 9001:2015 Compliance, 100%100% Factory Tested & Global Direct Delivery

Contact our specialized mission-critical data center liquid cooling engineering team today with your server rack power loads (kW), primary/secondary temperature targets, and facility layout for custom 3D CAD modeling proposals and factory-direct quotations.

PHONE

International Business:+86 0519 8878 2189

Domestic business:+86 0519 8878 2190

QUICK LINKS

PRODUCTS

ABOUT US

When it comes to building heat exchanger for any application VRCOOLERTECH has the capability to meet your requirements.
Copyright © 2021 Changzhou Vrcoolertech Refrigeration Co.,Ltd All rights reserved.  Sitemap  Manage Entrance