At CSTHEATEXCHANGER, we design and manufacture high-efficiency In-Rack Air-to-Liquid Coolant Distribution Units (In-Rack CDUs) specifically engineered with a maximum continuous heat dissipation capacity of 18kW for high-density AI compute nodes, multi-GPU training accelerators, edge data center enclosures, retrofitted legacy server racks, and high-performance computing (HPC) clusters (compact 4U to 6U rack-mountable chassis, dual redundant canned-rotor / magnetic-drive EC pumps with MTBF >100,000 hours, closed-loop liquid-to-air brazed aluminum microchannel or copper-tube/aluminum-fin heat exchangers, variable-speed high-static EC backward-curved blowers, and smart PLC/Modbus thermal regulation). CST 18kW in-rack air-to-liquid CDUs dissipate extreme chip-level thermal flux directly into room air without requiring facility chilled water infrastructure, maintain precise secondary coolant supply temperatures (typically +25°C to +40°C), deliver zero-drip blind-mate quick-disconnect reliability, and provide plug-and-play liquid cooling deployment inside standard 19-inch IT racks.

CSTHEATEXCHANGER 18kW In-Rack Air-to-Liquid CDU (Coolant Distribution Unit) for High-Density AI & Server Racks.jpg

1. Thermodynamic & Architectural Engineering: Chip-to-Rack Air-to-Liquid Heat Rejection

Modern high-density accelerator nodes (GPU, ASIC, FPGA) generate localized heat fluxes exceeding the physical cooling limit of traditional copper heatsinks and chassis fans. CST’s 18kW in-rack air-to-liquid CDU enables direct-to-chip (D2C) liquid cooling inside standard data center racks without expensive facility piping renovations:

        CST 18KW IN-RACK AIR-TO-LIQUID CDU HYDRONIC & THERMAL TOPOLOGY
        
   ======================= SERVER RACK COMPUTE LAYER (GPUS / CPUS) =======================
   (High-Flux Cold Plates on Multi-GPU Compute Nodes / Accelerators: 18kW Thermal Load)
   ┌────────────────────────────────────────────────────────────────────────────────────┐
   │ • Hot Secondary Coolant (+50°C to +60°C PG25/Water) leaves Cold Plates             │
   └────────────────────────────────────────┬───────────────────────────────────────────┘
                                            │ [HOT LIQUID LOOP TO CDU RETURN MANIFOLD]
                                            ▼
   ======================= CST 18KW IN-RACK CDU CHASSIS (4U/5U/6U) =====================
   ┌────────────────────────────────────────────────────────────────────────────────────┐
   │ [1. MICRO-DEBRIS STRAINER & EXPANSION RESERVOIR]                                   │
   │ • 50-micron stainless steel filter traps particulates; internal bladder deaerates  │
   ├────────────────────────────────────────────────────────────────────────────────────┤
   │ [2. N+1 REDUNDANT MAGNETIC DRIVE EC CIRCULATION PUMPS]                             │
   │ • Delivers constant 15–35 L/min secondary flow across multi-server cold plate loop │
   ├────────────────────────────────────────────────────────────────────────────────────┤
   │ [3. HIGH-EFFICIENCY AIR-TO-LIQUID HEAT EXCHANGER CORE & EC BLOWERS]                │
   │ • Brazed Aluminum Microchannel or Heavy-Duty Expanded Copper/Fin Coil Matrix       │
   │ • EC blowers draw rack air across coil; rejects 18kW heat directly to hot aisle    │
   └────────────────────────────────────────┬───────────────────────────────────────────┘
                                            │ [COOLED SUPPLY LIQUID: +30°C to +35°C]
                                            ▼
   ┌────────────────────────────────────────────────────────────────────────────────────┐
   │ • Cooled, de-aerated coolant returns to Server Quick-Disconnect Distribution Rack  │
   │ • Maintains chip junction temperatures well below throttling thresholds            │
   └────────────────────────────────────────────────────────────────────────────────────┘
================================================================================
CST 18KW IN-RACK AIR-TO-LIQUID CDU VS. FACILITY-TIED LIQUID-TO-LIQUID CDU
================================================================================
Evaluation Parameter           CST 18kW In-Rack Air-to-Liquid CDUTraditional Facility Liquid-to-Liquid CDU
--------------------------------------------------------------------------------
Facility Water Piping Needed   Zero Facility Chilled Water RequiredRequires heavy facility cooling loop & FWS pipes
Deployment Complexity & Speed  Plug-and-Play inside 19" Rack (Hours)Complex civil piping & building shutdown (Months)
Room Heat Rejection Path       Rejects directly to Hot Aisle / CRACRejects heat to building cooling tower / chiller
Rack Footprint / Form Factor   Compact 4U to 6U Rack-Mount Space Occupies bottom rack space or external row cabinet
Leakage Risk to Facility Floor Contained strictly inside single rackLong external plumbing runs across data hall floor
Pump Redundancy Standard       Dual N+1 Hot-Standby EC Mag PumpsDual N+1 Industrial Canned Pumps
Suitability for Edge AI / Labs Ideal for Edge Compute, R&D Labs, RetrofitOnly economical for large greenfield data centers
CapEx & Infrastructure Cost    Minimal Initial Infrastructure CostMassive facility hydraulic infrastructure CapEx
================================================================================

1. Zero-Plumbing Plug-and-Play Liquid Cooling Deployment

Traditional liquid-to-liquid CDUs require building-wide chilled water pipe loops, valves, and raised-floor penetrations. CST’s 18kW air-to-liquid CDU operates as a self-contained thermal conversion unit within the IT enclosure, drawing cold-aisle rack air across its internal high-performance heat exchanger and exhausting the 18kW thermal load into the room’s standard hot aisle or CRAC airflow.

2. Microchannel & Enhanced Fin Air-to-Liquid Coil Core

To extract 18kW of heat within a compact 4U–6U envelope, CST utilizes automotive-grade all-aluminum vacuum-brazed microchannel coils or high-density louvered copper-tube/aluminum-fin heat exchangers, paired with high-static pressure, pulse-width modulated (PWM) EC backward-curved fans to achieve maximum heat transfer coefficient with low airside pressure drop.

2. Hydraulic, Mechanical & Safety Engineering: Precision Coolant Management

Server liquid loops demand zero downtime, zero coolant leakage, and constant deaeration:

        CST 18KW IN-RACK CDU INTERNAL ARCHITECTURE
        
   ┌─────────────────────────────────────────────────────────────────────────┐
   │ [1. HYDRAULIC DRIVE & RESERVOIR MATRIX]                                 │
   │ • Dual N+1 hot-standby magnetic-drive EC pumps with seamless impellers. │
   │ • Stainless steel pressurized expansion reservoir with level sensing.   │
   │ • Integrated 50μm cleanable particulate filter and auto-air-bleed valve.│
   ├─────────────────────────────────────────────────────────────────────────┤
   │ [2. HEAT EXCHANGER & AIR-MOVING SYSTEM]                                 │
   │ • High-density brazed microchannel or expanded copper-fin radiator core.│
   │ • Hot-swappable, high-static PWM-modulated backward-curved EC blowers. │
   ├─────────────────────────────────────────────────────────────────────────┤
   │ [3. SAFETY & TELEMETRY SUITE]                                           │
   │ • Non-spill quick-disconnect couplings (Dry-Break / Blind-Mate).        │
   │ • Continuous rope-type leak detection sensors with auto-pump interlock. │
   │ • Smart PLC controller with Modbus-RTU, SNMPv3, and BACnet over IP.    │
   └─────────────────────────────────────────────────────────────────────────┘
       CST 18KW IN-RACK CDU MANUFACTURING WORKFLOW
       
   FROM PRECISION CNC-MACHINED MANIFOLDS & BRAZED CORES
   ┌─────────────────────────────────────────────────────────────────────────┐
   │ [ STAGE 1: HYDRAULIC VACUUM BRAZING & ORBITAL TIG WELDING ]             │
   │ Microchannel cores and SS304 distribution pipes welded under argon purge│
   ├─────────────────────────────────────────────────────────────────────────┤
   │ [ STAGE 2: 100% PRESSURE PROOF & MASS SPECTROMETER HELIUM TESTING ]     │
   │ Tested at elevated proof pressure; certified zero helium joint leakage  │
   ├─────────────────────────────────────────────────────────────────────────┤
   │ [ STAGE 3: N+1 PUMP COOLDOWN & CAVITATION ENDURANCE RUN ]               │
   │ Full hydraulic verification across simulated 18kW variable thermal loads│
   ├─────────────────────────────────────────────────────────────────────────┤
   │ [ STAGE 4: ADVANCED TELEMETRY & SENSOR CALIBRATION ]                    │
   │ Flow rate, delta-T, pressure, and multi-zone leak alarm verification    │
   └─────────────────────────────────────────────────────────────────────────┘
   DELIVERS MAXIMUM DATA CENTER RACK DOWNTIME IMMUNITY & LEAKAGE DEFENSE

1. N+1 Hot-Standby Magnetic Drive Circulation Pumps

CST integrates dual brushless DC / EC magnetic-drive pumps operating in an N+1 active/standby configuration. If the primary pump detects a drop in tachometer speed or flow, the secondary pump engages instantly without flow disruption, backed by an MTBF exceeding 100,000 continuous hours.

2. Multi-Zone Leak Detection & Auto-Interlock Safety

Liquid inside high-voltage server racks requires multi-tier safety. CST CDUs feature conductive rope-type leak sensing along the internal chassis drip pan and external manifold quick-disconnects, immediately triggering automated pump isolation, audible/SNMP alarms, and server emergency shutdown interlocks.

3. Product Variations: In-Rack Coolant Distribution Unit Series

        CSTHEATEXCHANGER IN-RACK CDU PORTFOLIO
        
   [1. CST-CDU-AIR-18KW (4U TO 6U CHASSIS)]
   • Standard 19-inch rack-mount air-to-liquid CDU delivering up to 18kW heat rejection.
   • Ideal for 1 to 4 high-density GPU servers, AI edge clusters, and enterprise lab enclosures.
   ─────────────────────────────────────────────────────────────────────────────
   [2. CST-CDU-AIR-30KW (6U TO 8U CHASSIS)]
   • High-capacity air-to-liquid CDU for full-rack accelerated computing (up to 30kW).
   • Dual high-flow microchannel arrays with high-CFM modular fan doors.
   ─────────────────────────────────────────────────────────────────────────────
   [3. CST-CDU-LIQUID-50KW TO 200KW+ (BOTTOM-OF-RACK / ROW-BASED)]
   • Liquid-to-liquid CDUs utilizing plate heat exchangers tied to facility chilled water.

4. Technical Specifications — 18kW In-Rack Air-to-Liquid CDU

(Note: The following engineering parameters represent standard manufacturing design envelopes. Exact dimensions, flow rates, pump head, and quick-disconnect fittings are custom-tailored to specific server cold plate loops, rack layouts, and data center air temperatures.)

================================================================================
CST 18KW IN-RACK AIR-TO-LIQUID CDU (CST-CDU-AIR-18KW)
================================================================================
Engineering Parameter           Typical Manufacturing & Design Range (Indicative)
--------------------------------------------------------------------------------
Maximum Heat Dissipation Duty   18 kW (61,400 BTU/h) Continuous Thermal Capacity
Cooling Medium Architecture     Air-to-Liquid (Rejects heat into Data Center Air)
Chassis Form Factor             Standard 19-Inch Rack Mount (4U, 5U, or 6U Height)
Secondary Coolant Flow Rate     15 L/min to 35 L/min (Modulated via EC Inverter)
Available Secondary Pump Head   1.5 bar to 3.0 bar (Overcomes multi-cold plate loss)
Pump Redundancy Architecture    Dual N+1 Hot-Standby Magnetic-Drive / Canned EC Pumps
Heat Exchanger Core Technology  Vacuum-Brazed Aluminum Microchannel / Copper-Alloy Fin Core
Blower & Fan System             N+1 Hot-Swappable Backward-Curved PWM EC Fans
Secondary Fluid Compatibility   Inhibited Propylene Glycol/Water (PG25/PG30), Deionized Water
Secondary Supply Fluid Temp     +25°C to +40°C (Dependent on Cold Aisle Air Temp)
Hydraulic Connection Standard   Dry-Break / Non-Spill Quick-Disconnect Couplings (1/2" or 3/4")
Particulate Filtration Standard 50 Micron Stainless Steel Cleanable / Replaceable Filter
Telemetry & Control Protocols   SNMPv3, Modbus-RTU / TCP, BACnet/IP, Web GUI, Dry Contacts
Safety & Protection Suite       Dual-Zone Drip Pan Leak Sensor, Low-Level & High-Temp Trip
Electrical Input Voltage        200–240V AC Single-Phase (50/60 Hz) / 48V DC Redundant Input
Testing & Quality Assurance     100% Mass Spectrometer Helium Leak Tested + Thermal Run Tested
================================================================================

5. Frequently Asked Questions (FAQ)

What is the operational difference between an air-to-liquid CDU and a liquid-to-liquid CDU?

A liquid-to-liquid CDU transfers server heat into an external building chilled water loop, requiring facility-level hydraulic piping. An air-to-liquid CDU (like this 18kW unit) transfers server liquid heat into its internal radiator core and expels it into the surrounding room or hot aisle via high-static fans, requiring zero external water plumbing and enabling instant deployment in any standard data center rack.

Can the 18kW in-rack CDU maintain safe GPU temperatures in high-ambient rooms?

Yes. Because direct-to-chip liquid cold plates have exceptionally low thermal resistance compared to air heatsinks, secondary coolant supply temperatures of +30∘C to +40∘C+30∘C to +40∘C easily maintain GPU and CPU junction temperatures well below thermal throttling limits, even when operating in standard +22∘C to +28∘C+22∘C to +28∘C cold aisles.

How does the unit safeguard server electronics against coolant leaks?

CST in-rack CDUs incorporate dry-break non-spill quick-disconnect couplings, 100% helium-tested vacuum-brazed coils, seamless welded stainless distribution piping, and continuous rope leak detection along the chassis base pan, automatically isolating pumps and alerting facility BMS via SNMP/Modbus upon any moisture detection.

Engineering Checklist for In-Rack CDU Sizing (Customer Confirmation Required)

To provide an exact custom thermodynamic calculation, pump curve selection, and dimensional CAD drawing for your server rack project, our engineering team requires confirmation of the following parameters:

================================================================================
PROJECT PARAMETERS FOR CUSTOM IN-RACK CDU SIZING
================================================================================
1. Total Rack Thermal Load:    Target dissipation capacity (e.g., 10 kW, 15 kW, 18 kW max)
2. Number of Compute Nodes:    Number of servers / GPU trays connected to the CDU loop
3. Cold Plate Loop Resistance: Estimated pressure drop across cold plates & manifolds (bar / PSI)
4. Target Secondary Supply T:  Required liquid supply temperature to cold plates (°C)
5. Rack Cold Aisle Air Temp:   Available room / cold-aisle air intake temperature (°C)
6. Available Rack Chassis U:   Maximum allowable rack height (4U, 5U, 6U, or custom)
7. Power Supply & Interface:   AC single-phase (220V) or DC (48V), plus required BMS protocol
================================================================================

Source Custom In-Rack CDUs from CSTHEATEXCHANGER

Unlock high-density AI compute performance without facility water piping renovation with CSTHEATEXCHANGER:

  • Custom In-Rack Air-to-Liquid CDUs (10 kW10 kW to 30 kW30 kW Capacity Envelopes)

  • Standard 19-Inch 4U / 5U / 6U Rack-Mount Form Factors

  • N+1 Redundant Magnetic-Drive EC Pumps with MTBF >100,000 Hours

  • Vacuum-Brazed Microchannel Radiators & Hot-Swappable High-Static EC Blowers

  • Non-Spill Quick Disconnects & Multi-Zone Rope Leak Detection Interlocks

  • Full Factory Helium Leak Testing & Global Direct Export

Contact our specialized data center thermal management engineering team with your rack layout, GPU cold plate flow rates, and room air parameters for custom CAD models and factory-direct quotations.

PHONE

International Business:+86 0519 8878 2189

Domestic business:+86 0519 8878 2190

QUICK LINKS

PRODUCTS

ABOUT US

When it comes to building heat exchanger for any application VRCOOLERTECH has the capability to meet your requirements.
Copyright © 2021 Changzhou Vrcoolertech Refrigeration Co.,Ltd All rights reserved.  Sitemap  Manage Entrance