For an efficient immersion cooling system with a dry cooler to support ~100 Antminer S21 miners, you'll need to carefully size the cooling capacity, select the right components, and ensure compatibility with immersion fluid. Here's a detailed breakdown:
1. Heat Load Calculation
Antminer S21 specs:
Power consumption: ~3,350W per miner (varies by model).
Total heat load: 100 × 3,350W = 335 kW (assuming 100% of power converts to heat).
Safety margin: Add 10–20% for peaks → Target cooling capacity: ~370–400 kW.
2. Immersion Cooling System Components
A. Immersion Tank & Fluid
Fluid type: Dielectric coolant (e.g., 3M Novec, Shell Immersion Fluid, or mineral oil).
Tank material: Stainless steel (corrosion-resistant) with sealed covers.
Fluid volume: ~500–1,000L (depends on tank design and miner spacing).
B. Dry Cooler (Closed-Loop)
Cooling capacity: 400 kW dry cooler (ambient air-cooled, no water needed).
Key features:
Material: Aluminum or coated fins (for corrosion resistance).
Fans: Variable-speed EC fans (for energy efficiency).
Pump: High-flow, low-pressure pump (compatible with immersion fluid).
Temperature range: Coolant outlet ≤ 50°C (to maintain miner efficiency).
C. Heat Exchanger (Optional)
If using a secondary loop, add a plate heat exchanger (stainless steel) to separate immersion fluid from the dry cooler loop.
3. Dry Cooler Sizing & Selection
Ambient conditions: Assume max ambient temp of 35°C (design for worst case).
Cooling approach: Target 10–15°C above ambient (coolant at ~45–50°C).
Dry cooler specs:
Type: Forced-air, V-frame or flat design.
Surface area: ~200–300 m² (depends on airflow and ΔT).
Airflow: 30,000–40,000 CFM (multiple fans for redundancy).
4. System Integration
Piping & Pumps:
Use stainless steel or EPDM hoses (compatible with coolant).
Pump head pressure: ~2–3 bar (ensure sufficient flow rate).
Controls:
PLC/thermostat to regulate fan speed and pump flow.
Alarms for high fluid temp or pump failure.
5. Maintenance & Longevity
Dry cooler: Clean fins quarterly (more often in dusty areas).
Immersion fluid: Check for degradation annually (replace every 3–5 years).
Miners: No dust buildup, but inspect for corrosion or leaks.
Conclusion
A 400 kW dry cooler paired with a sealed immersion system can efficiently cool 100 Antminer S21 miners, reducing energy use by ~30% compared to air cooling. Prioritize corrosion-resistant materials and smart controls for long-term reliability in harsh environments.
Main Functions and Applications of Industrial Gas-to-Gas Heat Exchangers
Water / Glycol Evaporators for Commercial and Industrial Cold Rooms
Titanium Plate Heat Exchanger (Evaporator) Customized to Specific Parameters
VRcoolertech CST Customized Fin Tube Steam Coils for Mexican Clients According to Drawings
Applications of Finned Tube Radiators in Industrial Settings
International Business:+86 0519 8878 2189
Domestic business:+86 0519 8878 2190