Views: 0 Author: Site Editor Publish Time: 2026-08-18 Origin: Site
Compatible model: INNIO Jenbacher J416 (16V) gas engine, with an electric power of approximately 1100-1250kW, used for biogas, landfill gas, and natural gas CHP cogeneration power plants.
Product form: HT-LT integrated remote dry cooler, fully based on the original engine thermal balance calculation book and project site boundary conditions for thermal calculation and whole machine customization, supporting new project matching and 1:1 replacement of old radiators.
HT high temperature circuit (cylinder liner water-cooled jacket water)
Heat dissipation: approximately 305 kW
Medium: Ethylene glycol aqueous solution
Working temperature: Inlet water 88-95 ℃/Return water 75-82 ℃
Function: Cooling of cylinder liner and cylinder head, maintaining the working temperature of the engine body
LT low-temperature circuit (intercooler+oil cooling Charge air+Lube oil)
Heat dissipation: 345 kW intercooled+175 kW engine oil
Working temperature: Inlet water 32-40 ℃/Return water 42-54 ℃
Function: Boost intake cooling, lubricating oil cooling, control intake temperature, avoid power attenuation in high-temperature environments
Top‑mounted Heat Pipe System Cabinet Heat Sink for Small Electrical Cabinets
Oval Tube Finned Heat Exchanger (Radiator), Custom Made per Drawings
Cost‑Saving Dry Cooler with Plate‑Fin & Micro‑Channel Coils for Data Center Liquid Cooling
5 Tons Rooftop Air Conditioning Unit Shipment to New Zealand | CST HEAT EXCHANGER
100% Fresh‑Air Rooftop Unit | Commercial Rooftop HVAC | cstheatexchanger.com
VRS63 Tube and Fin Radiator for Welding Machines Shipment to US Market
SUS 316L Finned Tube Radiator for Corrosive Industrial Heat Transfer Projects
International Business:+86 0519 8878 2189
Domestic business:+86 0519 8878 2190