Rear Door Heat Exchangers (RDHx) are typically sized by kW per rack, and the realistic capacity depends on whether it’s passive (no fans) or active (fans), plus the facility water temperatures and allowable pressure drop.
Passive RDHx (no fans)
~5–20 kW per rack typical
Best for moderate-density racks where you mainly want to knock down hot exhaust temperatures.
Limited by the rack’s own server fan power and the air-side pressure drop you can tolerate.
Active RDHx (with fans, often EC fans)
~20–60 kW per rack common
~60–100+ kW per rack is achievable with purpose-built designs (high airflow, larger coil face area, higher water flow, and tighter approach temperatures).
This is the dominant choice for high-density racks because airflow is controlled and predictable.
Airflow through the door (CMH/CFM)
More airflow = more heat you can capture at a given air ΔT.
Active RDHx can maintain airflow even at higher coil pressure drop.
Water-side conditions
Supply water temperature is huge: colder water increases capacity and reduces required coil size.
ΔT on water (e.g., 5–10°C typical) and available flow rate constrain kW.
Higher flow reduces approach temperature and boosts capacity, but increases pumping power.
Coil effectiveness & face area
Larger face area and deeper coils raise capacity while keeping air-side pressure drop reasonable.
Allowed air-side pressure drop
Passive systems are very sensitive here; active systems tolerate more.
Target outlet air temperature
If you only need “warm” exhaust vs. “near-ambient,” capacity and required water temperature change materially.
If you’re planning high-density (30–60+ kW/rack), assume active RDHx.
If you’re in the 10–20 kW/rack band and want simplicity, passive may work—if your rack/server fans can handle the added resistance.