RTU (Rooftop Packaged Unit)
Self-contained DX direct-expansion packaged unit, all refrigeration + air handling parts in one cabinet, mounted on roof.
Integrated inside: Compressor, condenser fan, cooling coil, supply fan, filters, dampers, heating module, controls.
No separate chiller / outdoor condenser required.
AHU (Air Handling Unit)
Only an air processing cabinet, no built-in refrigeration compressor.
Cooling/heating coils rely on external systems:
Chilled water from chiller plant (cooling)
Hot water / steam boiler (heating)
AHU only circulates, filters, temp-adjusts air via fluid coils.
Item | RTU (Rooftop Unit) | AHU (Air Handling Unit) |
|---|---|---|
Refrigeration System | Built-in compressor & condenser (DX system) | No compressor; uses chilled/hot water coils |
Installation Location | Mainly rooftop outdoor | Mechanical room, ceiling, basement (indoor) |
Cooling Source | Self-contained refrigerant circuit | Central chiller plant + water piping |
Heating Option | Gas furnace / electric heater / heat pump coil | Hot water coil, steam coil, electric heater |
Ventilation | Built-in fresh air dampers + economizer (free cooling) | Custom fresh air mixing section, ERV heat recovery optional |
Capacity Range | Small ~ medium: 5RT – 100RT | Small to ultra-large, unlimited size for big buildings |
Duct Static Pressure | Medium static (180–300Pa) | Can design high static for long complex ducts |
Space Requirement | No indoor mechanical room needed; uses roof space | Dedicated indoor mechanical room mandatory |
Initial Cost | Lower for single/mid-size buildings (no chiller) | Higher total investment (chiller + cooling tower + pumps + AHU) |
Running Cost | Higher for large multi-story buildings | More energy efficient for big central HVAC systems |
Maintenance | Roof access; service compressors, gas burners on roof | Indoor maintenance; chillers require separate upkeep |
Typical Projects | Retail stores, single-story offices, factories, warehouses, small malls | High-rise offices, hospitals, hotels, shopping malls, cleanrooms, data centers |
RTU Workflow
Return air + fresh air mix inside unit
Air passes DX cooling coil (refrigerant cools air)
EC/belt fan pushes conditioned air into building ducts
Compressor & condenser reject heat directly to outdoor rooftop air
AHU Workflow
Mix return air + outdoor fresh air
Air flows over chilled water coil (cold water from central chiller absorbs heat)
Fan delivers air to zones via ducts
Warm water flows back to chiller to be re-cooled by cooling tower
RTU Pros
All-in-one factory assembly, simple installation
No central chiller, no water piping system
Economizer free cooling saves power in mild weather
Ideal for single-story standalone buildings
RTU Cons
Multiple RTUs hard to centralize energy management
Less efficient for large multi-zone high-rise buildings
Outdoor unit needs climate anti-corrosion / high-temp upgrades
AHU Pros
Centralized cooling, better energy efficiency for large buildings
Precise temp/humidity control (hospital, cleanroom, cultivation)
Easy to add heat recovery, multi-stage filtration, ultra-clean sections
Scalable for thousands of square meters
AHU Cons
Needs full central plant (chiller, cooling tower, water pumps)
Higher upfront investment and complex piping construction
Occupies indoor mechanical room space