RTU vs AHU

Views: 0     Author: Site Editor     Publish Time: 2026-07-08      Origin: Site

RTU (Rooftop Packaged Unit)

Self-contained DX direct-expansion packaged unit, all refrigeration + air handling parts in one cabinet, mounted on roof.

Integrated inside: Compressor, condenser fan, cooling coil, supply fan, filters, dampers, heating module, controls.

No separate chiller / outdoor condenser required.

AHU (Air Handling Unit)

Only an air processing cabinet, no built-in refrigeration compressor.

Cooling/heating coils rely on external systems:

Chilled water from chiller plant (cooling)

Hot water / steam boiler (heating)

AHU only circulates, filters, temp-adjusts air via fluid coils.

Item

RTU (Rooftop Unit)

AHU (Air Handling Unit)

Refrigeration System

Built-in compressor & condenser (DX system)

No compressor; uses chilled/hot water coils

Installation Location

Mainly rooftop outdoor

Mechanical room, ceiling, basement (indoor)

Cooling Source

Self-contained refrigerant circuit

Central chiller plant + water piping

Heating Option

Gas furnace / electric heater / heat pump coil

Hot water coil, steam coil, electric heater

Ventilation

Built-in fresh air dampers + economizer (free cooling)

Custom fresh air mixing section, ERV heat recovery optional

Capacity Range

Small ~ medium: 5RT – 100RT

Small to ultra-large, unlimited size for big buildings

Duct Static Pressure

Medium static (180–300Pa)

Can design high static for long complex ducts

Space Requirement

No indoor mechanical room needed; uses roof space

Dedicated indoor mechanical room mandatory

Initial Cost

Lower for single/mid-size buildings (no chiller)

Higher total investment (chiller + cooling tower + pumps + AHU)

Running Cost

Higher for large multi-story buildings

More energy efficient for big central HVAC systems

Maintenance

Roof access; service compressors, gas burners on roof

Indoor maintenance; chillers require separate upkeep

Typical Projects

Retail stores, single-story offices, factories, warehouses, small malls

High-rise offices, hospitals, hotels, shopping malls, cleanrooms, data centers

RTU vs AHU.jpg

RTU Workflow

Return air + fresh air mix inside unit

Air passes DX cooling coil (refrigerant cools air)

EC/belt fan pushes conditioned air into building ducts

Compressor & condenser reject heat directly to outdoor rooftop air

AHU Workflow

Mix return air + outdoor fresh air

Air flows over chilled water coil (cold water from central chiller absorbs heat)

Fan delivers air to zones via ducts

Warm water flows back to chiller to be re-cooled by cooling tower

RTU Pros

All-in-one factory assembly, simple installation

No central chiller, no water piping system

Economizer free cooling saves power in mild weather

Ideal for single-story standalone buildings

RTU Cons

Multiple RTUs hard to centralize energy management

Less efficient for large multi-zone high-rise buildings

Outdoor unit needs climate anti-corrosion / high-temp upgrades

AHU Pros

Centralized cooling, better energy efficiency for large buildings

Precise temp/humidity control (hospital, cleanroom, cultivation)

Easy to add heat recovery, multi-stage filtration, ultra-clean sections

Scalable for thousands of square meters

AHU Cons

Needs full central plant (chiller, cooling tower, water pumps)

Higher upfront investment and complex piping construction

Occupies indoor mechanical room space