Low-noise Air Handling Units (AHUs) for hotels are designed to operate quietly (typically ≤35–40 dB(A)) while providing comfort, fresh air, and indoor air quality for guest rooms, lobbies, and public areas.
Core Requirements for Hotel AHUs
Noise: Guest rooms ≤32–35 dB(A); corridors/lobbies ≤40–45 dB(A)
Airflow: Guest rooms 30–50 m³/h per person; public areas per design code
Pressure: Medium-high static (150–300 Pa) for long duct runs
Filtration: G4+F8 (PM2.5) or higher for clean air
Heat recovery: Plate/enthalpy wheel to save energy
Key Low-noise Design Features
Fan & Motor:
EC/outer-rotor direct-drive (no belts, lower noise 3–5 dB)
Dynamic/static balancing + spring rubber isolators
Low-speed, high-efficiency centrifugal fans
Unit Construction:
Double-skin PU insulation (25–50 mm) for sound absorption
Air-tight, rigid cabinet to reduce vibration noise
Internal acoustic lining (polyester/foam)
Duct & System:
Low air velocity (main ≤6–8 m/s, branch ≤3.5 m/s)
Silencers at supply/return; flexible duct connectors
Vibration-isolated hangers and base rails