Views: 1 Author: Site Editor Publish Time: 2025-10-30 Origin: Site
Digital Agriculture Kiwifruit Ripening Cooling Evaporator
Core Requirements for Cold Air Coolers in Kiwifruit Ripening Processes
To understand the equipment's characteristics, one must first grasp the physiological ripening process of kiwifruit:
Precise Temperature Control: Kiwifruit ripening typically occurs within the 0°C to 20°C range, with strict requirements at different stages.
Initial Stage: Lower temperatures (e.g., 0-2°C) are used for extended storage to inhibit ripening.
Ripening Initiation: Temperatures must rise to 12-20°C (varies by variety; e.g., Hayward typically requires 14-16°C) to activate enzyme activity.
Critical Requirement: Temperature variation within the storage facility must remain below ±0.5°C to prevent uneven ripening.
Maximum Humidity: Relative humidity must be maintained at 90-95%.
Purpose: Prevents skin shriveling, preserves weight (directly impacting profitability), and achieves a plump appearance.
Ethylene Gas Management and Uniform Distribution:
Low-concentration ethylene (100-150 PPM) is used to trigger and synchronize the ripening process.
Ethylene gas must be uniformly distributed throughout the entire storage facility to ensure every kiwifruit crate is exposed to the same concentration.
Ventilation and Airflow Organization:
Gentle, uniform airflow is required to distribute temperature, humidity, and ethylene while removing heat and carbon dioxide (CO₂) produced by fruit respiration. Direct airflow onto fruit must be avoided to prevent localized dehydration.
Key Features of Kiwifruit Ripening Cold Air Cooler
To meet the above requirements, professional ripening cold air coolers incorporate the following design characteristics:
1. Dual/Multi-Directional Airflow Design
Delivers airflow from both sides or multiple directions, creating a uniform airfield that covers the entire storage room. This eliminates dead zones and ensures consistent temperature, humidity, and air distribution.
2. High Airflow Volume with Low Velocity
Fan configurations are engineered to move substantial air volumes while maintaining gentle airflow speeds. This ensures air penetrates stacked fruit bins to dissipate respiratory heat without causing fruit “wind-drying.”
3. Large Heat Exchange Area with High Sensible Heat Ratio
Multiple rows of copper heat exchange tubes enable “low-temperature-difference heat transfer.” This minimizes “excessive dehumidification” during cooling, maintaining stable high humidity at 90-95%.
4. Efficient Defrosting System
Evaporator frosting is inevitable in high-humidity, low-temperature environments. Hot gas defrosting is the optimal solution: it defrosts rapidly (5-10 minutes), minimally impacts storage temperature, and is more energy-efficient and safer than electric defrosting.
5. Corrosion-Resistant Design
Operating continuously in environments exceeding 90% humidity requires the cabinet, drip pans, fins, and other components to be constructed from epoxy resin-coated materials or stainless steel to prevent corrosion and leakage.
6. Deep Integration with Control Systems
The air cooler receives commands from the central controller and can coordinate with humidifiers, ethylene generators, and fresh air/exhaust valves to automatically operate according to preset ripening curves.
International Business:+86 0519 8878 2189
Domestic business:+86 0519 8878 2190