A liquid-to-liquid (L2L) CDU is the standard way to cool a direct-liquid-cooled HPC cluster at scale. It contains a plate heat exchanger that transfers heat from the clean, closed technology cooling loop (TCS) to the facility water loop (FWS), while keeping the two fluids physically separate. CSTHEATEXCHANGER manufactures gasketed and brazed plate heat exchangers in stainless steel for this duty, together with the dry coolers and free coolers that reject the facility-loop heat outdoors.

HPC clusters differ from single AI racks: they run many racks at steady, high utilisation for long jobs, so the cooling system must be sized for sustained load rather than peaks. This article explains what the L2L CDU's heat exchanger has to do and how we specify it.

L2L CDU for HPC cluster.jpg

Why HPC clusters use liquid-to-liquid CDUs

An HPC hall with dozens of liquid-cooled racks produces far more heat than room air can carry. The L2L CDU moves that heat straight into water:

  • The TCS stays clean. Cold plates and manifolds see only treated coolant from the CDU, never raw facility water, so corrosion and fouling inside the servers are controlled.

  • The FWS can run warm. Because the plate heat exchanger approach is small, facility water can often be supplied at temperatures that allow dry coolers to reject heat without compressors for much of the year.

  • One CDU serves many racks. Row- or hall-level CDUs with high-capacity plate heat exchangers reduce the number of pumps and controls to maintain.

The heat exchanger is the component that decides whether these benefits are real. An undersized or badly selected plate pack forces the facility loop colder than planned and erases the efficiency gain.

What CSTHEATEXCHANGER supplies for an L2L CDU and its facility loop

Loop position

Component

CSTHEATEXCHANGER scope

Inside the CDU

Plate heat exchanger (TCS ↔ FWS)

Gasketed or brazed plate heat exchanger in stainless steel (SS304 / SS316), selected for the required approach temperature and pressure drop; drawing supplied for approval

Outdoor heat rejection

Dry cooler / free cooler / hybrid or adiabatic cooler

Copper tube, aluminium fin dry coolers in hot-dip galvanized steel casings, pressure tested at 15 bar; adiabatic and hybrid variants for hot climates

Trim cooling

Water chiller

Air-cooled screw or water-cooled chillers for the hours when dry coolers alone cannot hold the FWS setpoint

Rack-level supplement

Rear Door Cooling Coil

For the air-cooled residual load of liquid-cooled servers (memory, drives, power supplies)

How CSTHEATEXCHANGER selects the plate heat exchanger for an HPC CDU

We size the plate heat exchanger from five inputs:

  1. Total cluster heat load at sustained utilisation, not nameplate.

  2. TCS supply temperature required by the cold plates and the allowable TCS ΔT.

  3. FWS supply temperature available from the dry cooler or chiller in the worst design month.

  4. Approach temperature — the gap between FWS inlet and TCS outlet. A smaller approach means a larger plate pack but a warmer facility loop and more free-cooling hours.

  5. Pressure-drop budget on both sides, which sets plate count and channel geometry.

Gasketed units are chosen when the customer wants the plate pack to be openable for inspection and capacity additions; brazed units when a compact, sealed exchanger is preferred. Both are supplied with material certificates and a pressure-test record.

L2L CDU design pitfalls we see in HPC projects

  • Sizing the plate heat exchanger for average load. HPC jobs run flat-out for hours. Size for sustained maximum.

  • Ignoring fouling on the facility side. Facility water is rarely as clean as the TCS. We apply a fouling margin and recommend strainers upstream.

  • Mixing materials. Copper in the TCS with aluminium cold plates, or carbon steel in the FWS with stainless plates, needs an inhibitor plan. We check compatibility during drawing review.

  • No redundancy on the heat exchanger. A single plate pack is a single point of failure for the whole cluster. Two half-size exchangers or an N+1 CDU arrangement is usually the better answer.

Frequently asked questions about CSTHEATEXCHANGER L2L CDU heat exchangers

What does the plate heat exchanger in an L2L CDU actually do?

It transfers heat from the closed technology cooling loop to the facility water loop without mixing the fluids, so the servers never see facility water.

Gasketed or brazed — which does CSTHEATEXCHANGER recommend?

Gasketed when you want to open, clean or add plates later; brazed when compactness and a sealed unit matter more. We quote both when the duty allows.

Can the facility loop run warm enough for dry coolers?

Often yes. A well-sized plate heat exchanger keeps the approach small, which lets the facility supply run warm and the dry cooler handle most hours. We model this per site.

Do you also supply the outdoor dry coolers?

Yes. Dry coolers, free coolers, hybrid and adiabatic coolers are part of our Air Cooling Unit range and are built to the same drawing-approval process.

Can you build the exchanger to our CDU frame drawing?

Yes. Send the frame drawing and loop data; we return a heat exchanger drawing with connection positions for approval before manufacturing.

Specify your HPC L2L CDU heat exchanger with CSTHEATEXCHANGER

Send CSTHEATEXCHANGER your cluster heat load, TCS and FWS temperatures, pressure-drop limits and CDU frame dimensions. We will return a plate heat exchanger selection, an outdoor dry cooler proposal if required, drawings for approval and a quotation.

CSTHEATEXCHANGER — plate heat exchangers and dry coolers for liquid-to-liquid CDUs, built to drawing.

PHONE

International Business:+86 0519 8878 2189

Domestic business:+86 0519 8878 2190

QUICK LINKS

PRODUCTS

ABOUT US

When it comes to building heat exchanger for any application VRCOOLERTECH has the capability to meet your requirements.
Copyright © 2021 Changzhou Vrcoolertech Refrigeration Co.,Ltd All rights reserved.  Sitemap  Manage Entrance